SPECI FI CATI ON S
UNISPEC II-STORE PLANNING 032307 2.4 WIRING DEVICES SECTION 16452 - TRACK BUSWAY SYSTEMS SECTION 16500 - LIGHTING
SECTION 16100-WIRING METHODS
A. BRANCH CIRCUIT SWITCHES: SPECIFICATION GRADE RATED 20A 120/277V AC AS FOLLOWS: PART 1- GENERAL PART 1- GENERAL
1. SINGLE POLE:
A. HUBBELL HBL1221GY. 1.1 SUMMARY 1.1 SUMMARY
PART 1 GENERAL B. PASS AND SEYMOUR PS20AC1-GRY. A. SECTION INCLUDES: A. SECTION INCLUDES
1.1 SUMMARY
C. COOPER 2221GY. 1. OWNER FURNISHED TRACK BUSWAY SYSTEMS. 1. LIGHTING FIXTURES. (OWNER FURNISHED)
A. SECTION INCLUDES: D. LEVITON 1221-2GY. 1.2 REFERENCES
1. WIRE AND CABLE. E. BRYANT 4901GRY.
1.2 QUALITY ASSURANCE
2. CONDUIT
A. THE PUBLICATIONS LISTED BELOW FORM A PART OF THIS SPECIFICATION TO THE EXTENT A. FIXTURES AND THEIR ELECTRICAL COMPONENTS WILL BEAR A UL ABEL.
3. OUTLET BOXES AND CONDUIT FITTINGS. B. RECEPTACLES - STRAIGHT BLADE NYLON GROUNDING - TYPE OUTLET DEVICES:
REFERENCED. PUBLICATIONS ARE REFERENCED WITHIN THE TEXT BY THE BASIC
4. WIRING DEVICES. SPECIFICATION GRADE AS FOLLOWS:
DESIGNATION ONLY. 1.3 DELIVERY, STORAGE, AND HANDLING
5. WIRE CONNECTORS. 1. DUPLEX RECEPTACLE 20A 125V (5-20R): B. UNDERWRITERS LABORATORIES (UL) A. STORAGE AND PROTECTION: PROVIDE PROPER FACILITIES FOR HANDLING AND STORAGE
A. HUBBELL HBL5362GY. 1. UL 857 - BUSWAYS OF MATERIALS TO PREVENT DAMAGE TO EDGES, ENDS AND SURFACES. KEEP MATERIALS
1.2 REFERENCES 6. PASS AND SEYMOUR 5362-GRY. DRY, FULLY PROTECTED FROM WEATHER. FIXTURES SHOWING SIGNS OF RUST OR
A. NATIONAL FIRE PROTECTION ASSOCIATION (NFPA): C. COOPER 5362GY. 1.3 QUALITY ASSURANCE WEATHERING WILL BE REPLACE AT CONTRACTORS EXPENSE.
1. NFPA 70 - NATIONAL ELECTRICAL CODE (NEC). D. BRYANT BRY5362GRY. A. TRACK BUSWAY AND ELECTRICAL COMPONENTS WILL BEAR A UL LABEL. B. CONTACT VENDOR AT LEAST 4 WEEKS PRIOR TO DESIRED DELIVERY DATE TO ARRANGE
B. UNDERWRITERS LABORATORIES (UL)
1. UL 1569 - METAL CLAD CABLES 1.4 DELIVERY, STORAGE, AND HANDLING
FOR DELIVERY OF LIGHTING FIXTURES.
PART 2 PRODUCTS
2 DUPLEX RECEPTACLE 20A 125V ISOLATED GROUND (5-20R): A. STORAGE AND PROTECTION: PROVIDE PROPER FACIUTIES FOR HANDLING AND STORAGE PART 2- PRODUCTS
A. HUBBELL IG5362GRY. OF MATERIALS TO PREVENT DAMAGE TO EDGES, ENDS, AND SURFACES. KEEP MATERIALS 2.1 OWNER FURNISHED PRODUCTS
2.1 WIRE AND CABLE
B. PASS AND SEYMOUR IG6300GRY. DRY AND PROTECTED FROM WEATHER. TRACK BUSWAY SHOWING SIGNS OF RUST OR
A. ELECTRICAL COMPONENTS AND DEVICES: LISTED AND LABELED AS DEFINED IN NFPA C. COOPER IG5362GY. WEATHERING SHALL BE REPLACED AT CONTRACTORS EXPENSE. A. OWNER'S LIGHTING VENDOR (HEREINAFTER REFERRED TO AS `NENDOR") WILL FURNISH
70, ARTICLE 100, BY A NATIONALLY RECOGNIZED TESTING AGENCY AND MARKED FOR D. LEVITON 5362-IGG. LIGHTING FIXTURES, LAMPS, AND PROTECT-A-LAMP COVERS, AS INDICATED ON
USE.
E. BRYANT BRY53621GGRY. B. CONTACT VENDOR AT LEAST 4 WEEKS PRIOR TO DESIRED DELIVERY DATE TO ARRANGE DRAWINGS, FOR INSTALLATION BY CONTRACTOR.
FOR DELIVERY OF TRACK BUSWAY.
B. WIRE AND CABLE SHALL BEAR UL LABEL AND SHALL CONFORM TO STANDARDS C. RECEPTACLES - LOCKING NYLON GROUNDING - TYPE OUTLET DEVICES: SPECIFICATION 2.2 LIGHTING FIXTURES (OWNER FURNISHED, CONTRACTOR INSTALLED)
ESTABUSHED FOR SUCH MATERIALS BY NATIONALLY RECOGNIZED AGENCIES. GRADE AS FOLLOWS:
PART 2- PRODUCTS
1. SINGLE LOCKING RECEPTACLE 15A 125V ISOLATED GROUND (L5-15R): 2.1 OWNER FURNISHED PRODUCTS
A. OWNER'S LIGHTING VENDOR(S): LIGHTING FIXTURES WILL BE SUPPLIED BY ONE OR MORE
OF THE FOLLOWING:
C. PROVIDE CODE GAUGE, SOFT ANNEALED COPPER WIRE, NOT LESS THAN 98 PERCENT A. HUBBELL IG4710.
A. THE TRACK BUSWAY SYSTEM WILL BE FURNISHED BY THE OWNER'S SUPPLIER FOR 1. ACUITYBRANDS LIGHTING (LITHONIA), CONYERS, GA, (800) 207-0363, WAL-MART
CONDUCTIVITY AND OF 600 VOLT CLASS. B. PASS AND SEYMOUR 1G4710.
G COOPER IGL515R. INSTALLATION BY THE CONTRACTOR. TEAM.
D. ALUMINUM ALLOY CONDUCTORS: SHALL NOT BE USED IN NEW CIRCUITS. D. LEVITON 4710-IG. 2.2 MANUFACTURERS
CHAD.SIMPSON@ACUITYBRANDS.COM
E. BRYANT 47101G. 2. CREE LIGHTING, MORRISVILLE, NC, (919) 287-7538. JENNIFER TALLENT.
E. CONDUCTORS: A. THE OWNER'S SUPPLIER WILL BE AS FOLLOWS
1. INSULATION TYPE SHALL BE ONE OF THE FOLLOWING: D. COVER PLATES: 1. STARLINE TRACK BUSWAY - CONTACT BRUCE HENRY OR RANDY MATHEWS, (501) PART 3- EXECUTION
A. THHN 1. NYLON COVER PLATES FOR FLUSH MOUNTED DEVICES. 821-6200 OR (866) 730-4816. EMAIL: walmartC megreps.com 3.1 INSTALLATION
B. THWN 2. GALVANIZED STEEL PLATES WHERE DEVICES ARE INSTALLED ON EXPOSED FITTINGS
C. XHHW OR BOXES. 2.3 TRACK BUSWAY SYSTEM (OWNER FURNISHED) A. INSTALL LIGHTING FIXTURES, LAMPS, LIGHTING PANELS, AND CONNECTIONS IN
D. XHHW-2 3. 302 STAINLESS STEEL COVER PLATES FOR RECESSED OUTLET BOXES IN MASONRY
A. DESCRIPTION AND RATINGS: THE TRACK BUSWAY SYSTEM SHALL BE AS INDICATED ON
ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS AND AS INDICATED ON
2. TYPE:
WALLS. DRAWINGS.
A. #10 AND SMALLER - STRANDED OR SOLID. 4. B ANK COVER PLATE ON ALL BOXES WITHOUT DEVICE. THE DRAWINGS AND IN ACCORDANCE WITH THE FOLLOWING:
B. #8 ANd LARGER - STRANDED
1. VOLTAGE RATINGS: 2-POLE, 480V MAX B. COORDINATE EXACT MOUNTING LOCATION OF LIGHTING FIXTURES WITH BUILDING
E. COLORS: 2. FREQUENCY: 60 HZ
STRUCTURE AND OTHER TRADES PRIOR TO INSTALLATION. CONTINUOUS ROWS SHALL BE
1. UNLESS OTHERWISE NOTED, WIRING DEVICES AND COVER PLATES SHALL BE GRAY 3. AMPACITY: 40A.
INSTALLED STRAIGHT AND TRUE.
F. INTERLOCKED ARMOR METAL CLAD (MC) CABLE: CONTRACTOR'S OPTION AS ALLOWED
NYLON.
BY AUTHORITIES HAVING JURISDICTION. MC CABLE SHALL HAVE THE FOLLOWING 4. COLOR: BLACK C. ATTACH FIXTURES TO CEILING GRID. INSTALL FOUR TO SIX FEET OF FLEXIBLE CONDUIT
CHARACTERISTICS:
2. BLANK COVER PLATES: ON BOXES WITHOUT DEVICES OR FIXTURES, PROVIDE SAME
5. CONDUCTORS: COPPER, 100 CONTINUOUS RATING AT AMBIENT TEMPERATURES FROM RECESSED FIXTURES INSTALLED IN LAY_IN CEILING GRID SYSTEMS TO OUTLET
TYPE AND COLOR AS THOSE INSTALLED ON DEVICES IN THE SAME ROOM OR AREA. BOXES SUPPORTED FROM BUILDING STRUCTURAL SYSTEM.
1. STANDARD MC. BELOW 40 DEGREES C/ 104 DEGREES F, ELECTRICALLY ISOLATED FROM THE
2. MINIMUM SIZE CONDUCTOR, #12 AWG COPPER, INCLUDING GREEN INSULATED 3. ISOLATED GROUND RECEPTACLES: ORANGE NYLON COVER PLATES WITH CIRCUIT
EQUIPMENT GROUND, SIZED IN ACCORDANCE WITH THE NEC. NUMBER ENGRAVED IN PLATE.
HOUSING. D. VERIFY CEILING AND WALL DETAILS. INSTALL FIXTURES COMPLETE WITH PROPER
3. OVERALL MOISTURE RESISTANT TAPE.
6. GROUNDING: ALUMINUM HOUSING AT 100% OR OPTIONAL ISOLATED GROUND BUS. MOUNTING ARRANGEMENTS FOR CEILING OR WALL CONSTRUCTION ENCOUNTERED.
4. GALVANIZED STEEL OR ALUMINUM INTERLOCKED CLADDING. 2.5 WIRE CONNECTORS 7. SYSTEM SHALL COMPLY WITH UL 857.
A. SPLICES:
E. WHERE INDICATED ON DRAWINGS, INSTALL PROTECT_A_LAMP COVERS AND CAPS.
5. MANUFACTURED IN ACCORDANCE WITH UL 1569.
1. #8 AWG AND SMALLER: IDEAL WINGNUT, 3M SCOTCHLOK, OR EQUAL CONNECTORS
B• FRAME AND ENCLOSURE: F. PROVIDE ADDITIONAL HARDWARE REQUIRED TO COMPLETE INSTALLATION SUCH AS NUTS,
OF PROPER SIZE. 3M N0. 567 IN-LINE SELF-STRIPPING CONNECTORS WILL BE
1. EXTRUDED ALUMINUM HOUSING ACTING AS 100 GROUND. BOLTS, THREADED RODS, AND UNISTRUT CHANNELS.
G. WIRE SMALLER THAN #12 AWG NOT PERMITTED UN ESS NOTED OTHERWISE. #14 AWG
PERMITTED ONLY AT BALLAST LEAD CONNECTIONS IN FLUORESCENT LIGHT ROWS. 2. HOUSING SHALL BE SLOTTED TO RECEIVE MOUNTING HANGERS FOR SUSPENSION FROM
TYPE MTW, OR TFF PERMITED FOR SIGNAL AND PILOT CONTROL CIRCUITS UNLESS 2. #6 AWG AND LARGER: SOLDERLESS LUGS AND CONNECTORS. STRUCTURE. 3.2 MAINTENANCE AND REPLACEMENT DURING CONSTRUCTION
NOTED OTHERWISE. 3. HOUSING SHALL BE OPEN ON THE BOTTOM TO ACCEPT PLUG-IN UNITS ANYWHERE A. PROVIDE MATERIAL AND LABOR TO DEEP CLEAN LIGHTING FIXTURES WITH ANTI-STATIC
PART 3 EXECUTION ALONG ITS LENGTH. CLEANING FLUID. REPLACE LAMPS WITH BUILDING PAINT OVERSPRAY ONE WEEK PRIOR
H. COLOR CODE: REFERENCE WIRING COLOR CODE SCHEDULE C. PROVIDE HARDWARE REQUIRED FOR A COMPLETE INSTALLATION SUCH AS NUTS, BOLTS, TO POSSESSION AT CONTRACTOR'S EXPENSE.
3.1 INSTALLATION - GENERAL THREADED RODS, T-BAR CLIPS AND UNISTRUT CHANNELS.
I. COLOR CODE #8 AWG AND SMALLER PHASE AND NEUTRAL CONDUCTORS BY A. INSTALL SPECIFIED MATERIALS IN ACCORDANCE WITH MANUFACTURER'S
B. MAINTAIN LIGHTING FIXTURES, BALLASTS AND LAMPS DURING CONSTRUCTION,
CONTINUOUS OUTER COVERING. CONDUCTORS #6 AWG AND LARGER MAY BE COLOR RECOMMENDATIONS. PART 3- EXECUTION POSSESSION, AND UNTIL STORE GRAND OPENING. COORDINATE REPLACEMENT OF
CODED BY TAPE. TAPE SHALL HAVE MINIMUM OF TWO COMPLETE WRAPS AROUND g, ALUMINUM ALLOY CONDUCTORS: SHALL NOT BE USED IN NEW CIRCUITS.
3.1 INSTALLATION (BY CONTRACTOR
DEFECTIVE, LOST, OR DAMAGED EQUIPMENT WITH VENDOR.
CONDUCTOR AT 6 INCHES FROM TERMINATIONS, SPLICES, AND JUNCTION POINTS. C. OWNER RESPONSIBILITY (INCLUDING VENDOR):
J. IDENTIFY CIRCUIT NUMBERS WITH SYNTHETIC CLOTH OR PLASTIC LABELS AT SPUCE
3.2 WIRE A. INSTALL TRACK BUSWAY SYSTEM IN ACCORDANCE WITH MANUFACTURER'S INSTALLATION
A. TIE WRAP GROUPS OF CONDUCTORS IN SWITCHBOARDS AND PANEL BOARDS. INSTRUCTIONS AND AS INDICATED ON THE DRAWINGS.
1. PROVISION FOR OVERSUPPLY OF 3 PERCENT ADDITIONAL LAMPS WITH INITIAL
AND JUNCTION POINTS.
LIGHTING FIXTURE SHIPMENT.
3.3 CONDUIT B. TRACK BUSWAY SECTIONS SHALL BE CONNECTED IN ACCORDANCE WITH THE 2. COSTS FOR REPLACEMENT FOR NORMAL FAILURE COVERED BY WARRANTY OF ANY
2.2 CONDUIT A. INSTALLATION: MANUFACTURER'S RECOMMENDATIONS UTILIZING CONNECTORS FURNISHED BY THE FIXTURE, LAMP, OR BALLAST PRIOR TO GRAND OPENING. EVALUATION OF
A. CONDUIT TYPES SHALL BE AS FOLLOWS AND SHALL BEAR UL OR ETL LABEL: 1. INSTALL CONDUIT CONCEALED, EXCEPT IN UNFINISHED AREAS AND WHERE INDICATED MANUFACTURER. ABNORMALLY HIGH FAILURE PERCENTAGE AND REPLACEMENT COVERED UNDER
WARRANTY WILL BE PROVIDED BY VENDOR ON SITE.
1. GALVANIZED RIGID METAL CONDUIT (GRC): HOT-DIP GALVANIZED. ON DRAWINGS. C. INSTALL MANUFACTURER FURNISHED END PIECES AND END CAPS AT THE ENDS OF EACH
2. INTERMEDIATE METAL CONDUIT (IMC): HOT-DIP GALVANIZED. 2. SUPPORT CONDUIT BY MEANS OF SPECIFIED HANGERS. RUN AND AS INDICATED ON THE DRAWINGS.
3. COSTS FOR REPLACEMENT OF PARTS DAMAGED DURING SHIPMENT. CHARGES WILL BE
3. ELECTRICAL METALLIC TUBING (EMT): HOT-DIP GALVANIZED. 3. DO NOT INSTALL CONDUIT UNDER SLAB UNLESS INDICATED ON DRAWINGS. CONDUIT MADE TO SHIPPING CARRIER OR RESPONSIBLE PARTY.
4. SCHEDULE 40 HEAVY-WAL PVC FOR ALL UNDERGROUND CONDUIT RUNS. INSTALLED BELOW SLAB SHALL BE GALVANIZED RIGID ME7AL (GRC), INTERMEDIATE D. CONTRACTOR RESPONSIBILITY:
5. FLEXIBLE METAL CONDUIT: ZINC-COATED STEEL OR ALUMINUM. METAL CONDUIT (IMC), OR SCHEDULE 40 PVC. PROVIDE EXTERIOR COATED GRC END OF SECTION 1. COORDINATE VENDOR ON-SITE EVALUATION OF ABNORMAL COMPONENT FAILURES OF
6. LIQUID TIGHT FLEXIBLE STEEL CONDUIT WITH PVC JACKET. BENDS AND ELBOWS FOR ALL UNDER GROUND CONDUIT. BALLAST AND LAMPS OVER 3 PERCENT OVERSUPPLY AT LEAST TWO WEEKS PRIOR
7. MC CABLE: STEEL OR ALUMINUM CLADDING. 4. ROUTE ABOVE GRADE CONDUIT PARALLEL OR PERPENDICULAR TO BUILDING LINES. TO GRAND OPENING. PROVIDE LABOR FOR ROUTINE AND NORMAL MAINTENANCE OF
5. MAINTAIN MINIMUM OF 6 INCHES CLEARANCE AT FLUES AND HEAT SOURCES. EQUIPMENT INCLUDING TROUBLESHOOTING AND DETERMINATION OF UGHTING FAILURE.
B. CONDUIT SIZES: SIZE CONDUtT IN ACCORDANCE WITH NEC UNLESS NOTED OTHERWISE 6. INSTALL GRC CONDUIT PENETRATING ABOVE GRADE OUTDOORS OR PENETRATING 2. MATERIAL AND LABOR COSTS FOR REPLACEMENT OF LOSS, BREAKAGE, OR OTHER
ON DRAWINGS, BUT NOT LESS THAN THE FOLLOWING: CONCRETE SLABS, INCLUDING ELBOW. DAMAGE DUE TO FAULT OF CONTRACTOR INCLUDING LAMPS WITHIN THE 3 PERCENT
1. ALARM AND DATA SYSTEMS: 3/4 INCH. 7. INSTALL GRC ELBOW ON ALL CONDUIT RUNS THAT HAVE 45° BENDS OR GREATER. INITIAL OVERSUPPLY.
2. FLEXIBLE METAL CONDUIT: FOR CONNECTION OF RECESSED LIGHT FIXTURES IN 8. INSTALL DOUBLE LOCKNUT AND BUSHINGS WHEN TERMINATING GRC OR IMC CONDUIT,
SUSPENDED CEILINGS, 3/8 INCH. FOR CONNECTION OF OTHER EQUIPMENT EXCEPT WHERE CONDUIT TERMINATES IN THREADED HUB.
3. CONTACT VENDOR TO ORDER REPLACEMENT PARTS IN TIME TO HAVE ALL FIXTURES
FULLY OPERATIONAL PRIOR TO GRAND OPENING.
SUBJECT TO VIBRATION: 1/2 INCH.
B. LOCATION: E. REPLACEMENT PROCEDURE - GENERAL•
3. UNDERGROUND CONDUIT IN PARKING LOT: 1 INCH.
1. GALVANIZED RIGID METAL CONDUIT (GRC): PERMITTED FOR GENERAL EXPOSED OR 1. IMMEDIATELY NOTIFY VENDOR AND REQUEST REPLACEMENT OF DAMAGED FIXTURES,
4. OTHER USES: 1/2 INCH. CONCEALED WORK ABOVE OR BELOW GRADE. BALLASTS OR LAMPS DELIVERED TO THE JOBSITE.
2.3 OUTLET BOXES AND CONDUIT FITTINGS 2. INTERMEDIATE METAL CONDUIT (IMC): PERMITTED FOR GENERAL EXPOSED OR 2. IF SHIPPING DAMAGE IS CONCEALED, NOTIFY CARRIER AND VENDOR WITHIN 15 DAYS
A. OUTLET BOXES AND CONDUIT FITTINGS SHALL BEAR UL OR ETL LABEL. CONCEALED WORK ABOVE OR BELOW GRADE. OF ACCEPTANCE OF THE FREIGHT. PROVIDE VENDOR A COPY OF THE WRITTEN
3. ELECTRICAL METALLIC TUBING (EMT): PERMITTED FOR GENERAL EXPOSED OR NOTIFICATION SENT TO THE CARRIER.
B. BOXES: COMPLY WITH NEC IN REGARD TO MAXIMUM ALLOWABLE NUMBER OF CONCEALED WORK ABOVE GRADE. 3. USE 3 PERCENT LAMP OVERSUPPLY FOR REPLACEMENT FOR ANY REASON PRIOR TO
CONDUCTORS. 4. FLEXIBLE METAL CONDUIT: PERMITTED IN ATTIC SPACES AND EXPOSED IN LENGTHS GRAND OPENING. ORDER ADDITIONAL LAMPS ONLY AFTER OVERSUPPLY IS EXHAUSTED.
1. INTERIOR BOXES: HOT-DIP GALVANIZED, 4 INCHES MINIMUM OCTAGON OR OF 6 FEET OR LESS FOR CONNECTIONS TO EQUIPMENT IN DRY AREAS. NOT
SQUARE, UNLESS OTHERWISE NOTED. PROVIDE SINGLE OR MULTIPLE GANG PERMITTED FOR GENERAL EXPOSED OR CONCEA ED WORK. FOR CONNECTION OF A. MAINTAIN ACCOUNTING LOG FOR DISPOSITION OF LAMP OVERSUPPLY. IDENTIFY ON LOG,
OUTLET BOXES AS REQUIRED FOR FLUSH INSTALLATION IN DRYWALL RECESSED LIGHT FIXTURES IN SUSPENDED CEI INGS AND CONNECTION OF OTHER THE DATE, LOCATION, AND REASON FOR REPLACEMENT OF EACH LAMP USED FROM THE
CONSTRUCTION. PROVIDE MASONRY BOXES FOR OUTLETS INSTALLED FLUSH EQUIPMENT SUBJECT TO VIBRATION.
OVERSUPPLY.
IN CONCRETE UNIT MASONRY. PROVIDE SINGLE SURFACE-MOUNTED OUTLET 5. LIQUID TIGHT FLEXIBLE METAL CONDUIT: PERMITTED EXPOSED IN LENGTHS OF 6 B. RETAIN LOG FOR REVIEW BY VENDOR AND OWNER FOR DETERMINATION OF COST
BOXES FOR UTILITY TYPE BOXES. FEET OR LESS FOR CONNECTIONS TO FOOD SERVICE EQUIPMENT, REFRIGERATION WI RI N G COLOR CODE SCH EDU LE RESPONSIBILITY.
2. OUTLET BOXES: SUITABLE FOR SUPPORTING LIGHTING FIXTURES IF INTENDED EQUIPMENT AND OTHER VIBRATING EQUIPMENT IN DAMP LOCATIONS WHERE RIGID
FOR THAT PURPOSE. CONNECTIONS ARE NOT SUITABLE. g.Qp F. ADDITIONAL BALLAST REPLACEMENT PROCEDURE:
1. ORDER REPLACEMENT BALLAST FROM VENDOR. REQUEST RETURN AUTHORIZATION
C. CONDUIT FITTINGS 3.4 WIRING DEVICES NUMBER FROM VENDOR TO RETURN DEFECTIVE BALLAST N0 LATER THAN GRAND
1. INDOOR EMT FITTINGS: DIECAST OR STEEL SET SCREW TYPE. A. REPLACE OUTLETS OR DEVICES IMPROPERLY LOCATED OR INSTALLED. SET OUTLETS SYSTEM VOLTAGE NEUTRAL COLOR PHASE GROUND ISOLATED GROUND OPENING.
2. THREADLESS GRC OR IMC FITTINGS: NOT PERMITTED. AND DEVICES PLUMB OR HORIZONTAL AND EXTEND T0, BUT NOT PROJECT ABOVE, 2. RETURN ALL DEFECTIVE BALLAST TO VENDOR. VENDOR WILL ARRANGE PICKUP AND
3. INDOOR GRC OR IMC CONNECTORS. FINISHED SURFACE. RETURN, INCLUDING SHIPPING COSTS, OF DEFECTIVE BALLAST. COST FOR BALLAST
4. LOCKNUTS AND BUSHINGS NOT RETURNED WITHIN THE SPECIFIED TIME FRAME OR RETURNED BUT NOT
B. UNLESS OTHERWISE NOTED, RECEPTACLES, SWITCHES, AND OTHER WIRING DEVICES 208/120V
WHITE A-BLACK GREEN GREEN W/ YELLOW TRACER DEFECTIVE WILL BE AUTOMATICALLY CHARGED TO CONTRACTOR.
SHALL NOT BE MOUNTED BACK-TO-BACK. B-RED
C-BLUE END OF SECTION
END OF SECTION
It. GRAY OR WHITE WITH
A-BROWN GREEN GREEN W/ YELLOW TRACER
480/277V
COLORED STRIPE OTHER
B_ORANGETHANYELLOW
C-YELLOW
LIGHTING FIXTURE SCHEDULE
NOTE: ALL FlXTURES AND LAMPS ARE FURNISHED BY OWNER FOR INSTALLATION BY THE CONTRACTOR UNLESS NOTED OTHERWISE ON THE DRAWINGS.
LAMP PHILIPS
TYPE VENDOR CATALOG NUMBER VOLTS WATTS ORDER NUMBER QTY MOUNTING DESCRIPTION
16 LITHONIA LQM S W 1 R 120/277 ELN SD90 120/277 1 INTEGRAL LED - WALL EXIT SIGN (SINGLE FACE)
17C LITHONIA ELM2 SD90 B 120/277 2 6V, 6W SEALED HALOGEN 2 WALL EMERGENCY LIGHT
51 LITHONIA WM4 120 4 INTEGRAL LED - SUSPENDED GLASS PENDANT LIGHT
53C LITHONIA LWR9 1 G 28T5 HOL U4 277 GEB10 LP850 C201 277 26 F28T5/850/HO/ALTO 1 RECES5ED WALL WASH FIXTURE
57 CREE TDG38-B-GU24-BL 120 12 LRP38-GU24 1 BUSWAY SPOTLIGHT-SPECIALTY
PROFESSIONAL ENGINEER
1 HEREBY CERTIFY THAT THIS PLAN SPECIFICAl10N, OR
REPORT WAS PREPARED BY ME OR UNDER MY DIRECT
SUPERVISION AND THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE LAWS OF THE
STATE OF MINNESOTA.
PRINT NAME:
SIGNATURE: '
DATE _' ' 'u LICENSE 40241 _
ZyO
W
W
Q
W'f
TW
W W o
vioZ a'
oo Z ZWF wQ3NW
S O i`
z zww
aa -o JoovW,=za^'
w zaQ w F00
av' aor-z a
W
o
v rnc a a o v
Q i QWWfn Waa'
3 zWw o Wa oa
c a Q ok'v i a zZ
a o```
cw.
r'c i
Z OJU WU,WjZUW
w z'k-'aow oo aor
tn OQ NW ZK a
c orna aawoa
0 D
0 0
U ..N
wo
O
ww
W
O
0
w
GA
0
CHECKED BY: OM
DRAWN BY: CDK
DOCUMENT DATE: 05/19/10
PROTO:
SPECIFICATIONS
AND
SCHEDULES
SHEET:
E2