2016-00731
AHU - SEQUENCE OF OPERATION OCCUPIED SETPOINTS - 73 DEG F (COOLING) 68 DEG F (HEATING) UNOCCUPIED SETPOINTS - 82 DEG F (COOLING) 60 DEC F (HEATING) MECHANICAL CONTRACTOR TO PROGRAM AHU WALL MOUNTED THERMOSTAT TO HAVE THE SET POINTS LISTED ABOVE. SEE EN12 FOR TIME SCHEDULE GAS COMPANY: CENTERPOINT ENERGY CONTACT NAME: MARK SPANTON GENERAL NOTES PHONE NUMBER: 877-809-3803 EXISTING GAS LOAD = 15233 MBH GAS LOAD REMOVED = 0 MBH GAS LOAD ADDED = 60, MBH NEW GAS LOAD 15293 MBH NATURAL GAS 07,26. 13 PIPING NOTES i CONTRACTOR SHALL COORDINATE ALL DETAILS OF THE GAS PIPING SYSTEM WITH THE LOCAL GAS COMPANY. THIS INCLUDES, BUT IS NOT LIMITED TO, THE LOCATION OF THE GAS METER, GAS PRESSURE REQUIREMENTS, RELOCATION AND/OR UPSIZING OF EXISTING SERVICE PIPING IF REQUIRED. CONTRACTOR SHALL PAY ALL COSTS REQUIRED BY GAS COMPANY. CONTACT GAS COMPANY FOR SIZE AND TYPE OF PIPING AND 'VALVES REQUIRED FOR CONNECTION TO METER. GAS METER AND SERVICE REGULATOR TO BE PROVIDED BY UTILITY COMPANY. VERIFY CORRECT GAS PRESSURE Dr)kVNSTREAM OF SERVICE REGULATOR AFTER GAS UTILITY COMPLETES INSTALLATION. THE NATURAL GAS DEMAND SHOWN IN MBH IS BASED ON A HEATING VALUE OF 1000 BTU (I MBH) PER CUBIC FOOT, A SPECIFIC GRAVITY OF 0.6, AND ON PRIMARY EQUIPMENT SPECIFICATIONS IN SCHEDULES. GAS PIPING SIZES SHALL. BE AS NOTED ON PLANS. 2. CONTRACTOR SHALL PROVIDE AND INSTALL ALL GAS PIPING UP TO AND INCLUDING THE REGULATOR AND FINAL CONNECTION TO THE EQUIPMENT. REFERENCE MECHANICAL SHEETS FOR ALL PIPE CONNECTIONS AND ROUTING. REMOVE UNUSED GAS-PI.Pt "C'm PESAN, W, 011P WCi" FOR t4EVV R V RNRPEU_WL&Aff CONNECT'EXISTING G I A-9TI I OR GAS PIPING OF EQUAL OR LARGER SIZE, AND PROVIDE PRESSURE REGULATOR (SET TO EQ1 IIPMENT DELIVERY PRESSURE), VALVES, AND ACCESSORIES PER THE SPECIFICATIONS & LOCAL CODES, 4. GAS AND CONDENSATE PIPING SHALL BE MINIMUM 5-0" CLEAR FOR ROOF TOP EQUIPMENT MAINTENANCE ACCESS. 5. PROVIDE START -UP ASSISTANCE FOR ALL GAS-FIRED EQUIPMENT INCLUDING BUT NOT LIMITED TO ROOFTOP UNITS, RADIANT HEATERS, UNIT HEATERS, AND COOKING EQUIPMENT, COORDINATE ADJUSTMENT OF REGULATORS WITH SET-UP PERSONNEL TO ENSURE CORRECT GAS FLOW PRFRSURF',.; FOR PROPER OPERATION OF ROOF CURB. DO NOT SET RTU DIRECTLY ROUND DUCTWORK OF EQUIVALENT FREE 2WY O4HOURSPRIORTOSHUTTINGDONANN ROOF- COORDINATE RTU AREA MAY BE USED IN LIEU OFFHVACSYSTEMS, HVAC SYSTEMS, OR ENERGY INSTALLATION WITH WAL-MART RECTANGULAR. INCREASE RECTANGULAR MANAGEMENT CONTROLS SYSTEMS, SEND E- CONSTRUCTION MANAGER AND AES AS SHEET METAL SIZE AS REQUIRED FOR WALMART.COM. THE MAIL TO NSRM@ ' REQUIRED FOR RTUIAHU CURB ADAPTERS, LINER, REFER TO SPECIFICATIONS FOR SHALL STATE WHAT, WHY, AND WHEN IT IS THE INSULATION THICKNESS. BEING SHUT DOWN AND HOW LONG IT IS & REPLACE FILTERS ON NEW RTU NO MORE ANTICIPATED TO BE DOWN. THEN SEND A THAN ONE DAY PRIOR TO STARTING TEST 19. DUCT SUPPORT AND GRILLE DETAIL IS FOLLOW UP EAMAIL TO NSRlv!@WALMART,COM & BALANCE PROCEDURES. FILTERS SHALL APPLICABLE THROUGHOUT THE STORE, DO AFTER THE WORK IS COMPLETE AND THE BE 2" THICK EQUAL TO FARR 30/30. NOT USE FASTENERS THAT PENETRATE ROOF SYSTEM IS BACK UP AND RUNNING. DECK, 9. LABEL RTU WITH 6" BLACK PERMANENT PAINT STENCIL AND LABEL SENSOR WITH 20, TYPICAL BRANCH DUCT FITTING DETAIL IS 2" Hf(3H BLACK PERMANENT PAINT APPLICABLE THROUGHOUT THE STORE. STENCIL, NUMBER THE SENSOR TO CORRESPOND WITH RTU IT CONTROLS, 21. PROVIDE SEISMIC BRACING BASED ON LOCATE LABEL FOR UNIT NEAR ITS APPROPRIATE SEISMIC ZONE REQUIREMENTS DISCONNECT SO IT IS READABLE FROM PER SMACNA PUBLISHED SEISMIC DETAILS, ROOF HATCH. LOCAL AND NATIONAL CODES. CONTRACTOR'S RESPONSIBILITY INCLUDES STRUCTURAL 10. IF RTUS ARE INSTALLED BEFORE ROOFING ENGINEER'S CERTIFICATION ON DETAILS JAPPROVED FJ LF_ 'COOPY w. ISSUE BLOCK Building Official Review and aUWLC`I_T0 H&,j j9wS;,jzfZ- uN A, At, Required Prior To Changes, Modiftations, Date or Alterations 235 MBIA Separate Application And Permits Required Sewer/Water Connection Heating and Air Conditioningj RTU -36 Fire Alarm System 10 TON Plumbing ROOF_... ETR DRAINS CETR U4 TYP) CHECKED BY, ic 4 828 MBH TO MAU ETR 2 BOAS -1 M 1 60 MBH,-,._ VERIFY GAS PRESSURE PRIOR TO START OF WORK 1/4"G ETR REFER TO MANUFACTURER'S INSTALLATION INSTRUCTIONS FOR ROUTING OF LIQUID AND SUCTION LINES TO ROOF MOUNTED CONDENSING UNITS. MAINTAIN ALL REQUIRED WORKING CLEARANCES, TYP OF ALL) DRAWINGS AND MAY NOT REFLECT EXACT "AS -BUILT" THOROUGH KNOWLEDGE OF ALL DliAWNU,5 ANU MECHANICAL ROOF PLAN CONDITIONS. CONTRACTOR SHALL FIELD VERIFY ALL SPECIFICATIONS IN THEIR RELATED FIELD. THE FAILURE EXISTING CONDITIONS PRIOR TO SUBMITTING FINAL TO ACQUAINT THEMSELF WITH THIS KNOWLEDGE DOES 114" V-041 BIDS. CONTRACTOR SHALL CAREFULLY COORDINATE NOT RELIEVE THE RESPONSIBILITY OF PERFORMING THE SHEET: NEW WORK AND DEMOLITION WITH ALL OTHER WORK PROPERLY. NO ADDITIONAL COMPENSATION DISCIPLINES AND EXISTING CONDITIONS, SHALL BE ALLOWED BECAUSE OF CONDITIONS THAT OCCUR DUE TO FAILURE TO FAMILIARIZE WORKERS WITH M 1 THIS KNOWLEDGE- MECHANICAL KEYNOTES GENERAL NOTES 17. FLEXIBLE DUCT CONNECTIONS TO NEW OR SLOPE OF ROOF, 7. CONTRACTOR SHALL INSTALL OWNER RELOCATED DIFFUSERS AND GRILLES ARE X, Y FURNISHED RTU CURB AND TEMPORARY PROHIBITED. INSPECT CONDITION OF Xnx, SEE SPECIFICATION FOR ADDITIONAL INFORMATION, COVER CURB PER ARCH DETAIL (IF 5,617 COORDINATE REFRIGERATION LtNE 1. GENERAL NOTES ARE APPLICABLE TO ALL 12 MECHANICAL FAILURE OF NEW ROOFTOP BY OWNER, USED), RTU'S SHALL BE FURNISHED BY DUCT WITH EQUIVALENT TYPE OF DUCT AS PENETRATIONS THROUGH THE ROOF. MECHANICAL DRAVOINGS. UNITS PRIOR TO ACCEPTANCE SHALL BE REPAIRED OR REPLACED BY OWNER AND INSTALLED BY CONTRACTOR. REQUIRED, REINFORCE ROOF STRUCTURE AS 2. PROVIDE ALL MATERIALS FOR A COMPLETE CONTRACTOR THROUGH WARRANTY LU NECESSARY, CUT THE ROOF FOR THE REFRIGERATION PIPE PENETRATION, AND INSTALLATION IN ALL RESPECTS AND READY AGREEMENT WITH MANUFACTURER. FURNISHED BY OWNER AND INSTALLED BY 18. DUCT SIZES SHOWN ON DRAWINGS ARE NET SUPPLY THE PIPE PENETRATION RAIN HOOD. FOR INTENDED USE AND IN STRICT ACCORDANCE WITH STATE AND LOCAL CODES 13, IF APPLICABLE, COORDINATE ALL NEW CONTRACTOR RTU SHALL BE SET ON FREE AREA, CONTRACTOR'S OPTION, PROPERLY FLASH, PATCH, AND REPAIR ROOF AND MANUFACTURERS RECOMMENDATIONS. GAS PIPING AND ROOF EQUIPMENT WITH AS REQUIRED FOR NEW PENETRATION, SEAL EXISTING GAS PIPING, SKYLIGHTS, AND THE ROOF OPENING WITH FOAM AS SOON AS THE PIPING THROUGH THE ROOF OPENING IS 3, STORE MUST BE KEPT IN OPERATION. ROOF EQUIPMENT. FIELD VERIFY COMPLETE. ARRANGE ALL WORK TO KEEP DISRUPTIONS EXISTING CONDITIONS. TO STORE OPERATIONS TO A MINIMUM, 15.711 REFER TO ARCHITECTURAL ROOF PLAN AND COORDINATE WITH EXISTING AND NEW 14, ROOFTOP UNITS BEING ADDED TO STRUCTURAL PLANS FOR DETAILS OF ROOF CONSTRUCTION. PAY ALL NECESSARY EXISTING ROOF STRUCTURE SHALL BE CURB INSTALLATION, FEES AND PERMITS. INSTALLED WHEN THE UNITS ARRIVE AT THE JOB SITE, REFERENCE 0, 4, IF NEW CONSTRUCTION DISRUPTS ARCHITECTURAL/STRUCTURAL SHEETS FOR LU 0 ! x EXISTING UNDERGROUND SERVICES (GAS, DETAILS. I 121 `0' 29 z., b ROOF CURB NOTE SEWER, DOMESTIC WATER, FIRE zu) t E W, 3 6 3 SPRINKLER, ETC.), PROVIDE ALL 15, NOT USED. cr_ j;7_ 5 0 07.26-13MATERIALS AND LABOR AS REQUIRED TO ter= 1z z < MAINTAIN THEIR PROPER OPERATION. 16. COORDINATE LOCATION OF DUCTWORK AND z OWNER SHALL FURNISH AND THE CONTRACTOR SHALL DIFFUSERS WITH LIGHT FIXTURES TO 0 Zw INSTALL ROOF CURB AS MANUFACTURED BY AES 5. CONTRACTOR IS RESPONSIBLE FOR PREVENT EXCESSIVE SHADOWING OF THE RotL, 0 INDUSTRIES INC., CONTACT CHAD BURT 1-800-786-0402) UTILIZING OWNER APPROVED ROOFING SALES OR STOCK FLOORS, LIGHT FIXTURE j M 086t. WUin > paFORNEWROOFTOPUNITS. ROOF CURB SELECTIONTIPCONTRACTORSFORCUTTINGANDLOCATIONSTAKEPRECEDENCE. FIELD Wtl_ < _--mz 0 4 z W Q - 0 AND INSTALLATION SHALL BE ADJUS] -ED FOR ROOF PATCHING ROOF. VERIFY STRUCTURAL CONDITIONS BEFORE a -:nSZ911jWt)= 1 0ML000 SLOPE TO MAINTAIN LEVEL RTU INSTALLATION AND FABRICATION OF DUCTWORK. ADEQUATE CONDENSATE DRAINAGE, ROUTE NEWa RWIT USED"Q ROOF CURB. DO NOT SET RTU DIRECTLY ROUND DUCTWORK OF EQUIVALENT FREE 2WY O4HOURSPRIORTOSHUTTINGDONANN ROOF- COORDINATE RTU AREA MAY BE USED IN LIEU OFFHVACSYSTEMS, HVAC SYSTEMS, OR ENERGY INSTALLATION WITH WAL-MART RECTANGULAR. INCREASE RECTANGULAR MANAGEMENT CONTROLS SYSTEMS, SEND E- CONSTRUCTION MANAGER AND AES AS SHEET METAL SIZE AS REQUIRED FOR WALMART.COM. THE MAIL TO NSRM@ ' REQUIRED FOR RTUIAHU CURB ADAPTERS, LINER, REFER TO SPECIFICATIONS FOR SHALL STATE WHAT, WHY, AND WHEN IT IS THE INSULATION THICKNESS. BEING SHUT DOWN AND HOW LONG IT IS & REPLACE FILTERS ON NEW RTU NO MORE ANTICIPATED TO BE DOWN. THEN SEND A THAN ONE DAY PRIOR TO STARTING TEST 19. DUCT SUPPORT AND GRILLE DETAIL IS FOLLOW UP EAMAIL TO NSRlv!@WALMART,COM & BALANCE PROCEDURES. FILTERS SHALL APPLICABLE THROUGHOUT THE STORE, DO AFTER THE WORK IS COMPLETE AND THE BE 2" THICK EQUAL TO FARR 30/30. NOT USE FASTENERS THAT PENETRATE ROOF SYSTEM IS BACK UP AND RUNNING. DECK, 9. LABEL RTU WITH 6" BLACK PERMANENT PAINT STENCIL AND LABEL SENSOR WITH 20, TYPICAL BRANCH DUCT FITTING DETAIL IS 2" Hf(3H BLACK PERMANENT PAINT APPLICABLE THROUGHOUT THE STORE. STENCIL, NUMBER THE SENSOR TO CORRESPOND WITH RTU IT CONTROLS, 21. PROVIDE SEISMIC BRACING BASED ON LOCATE LABEL FOR UNIT NEAR ITS APPROPRIATE SEISMIC ZONE REQUIREMENTS DISCONNECT SO IT IS READABLE FROM PER SMACNA PUBLISHED SEISMIC DETAILS, ROOF HATCH. LOCAL AND NATIONAL CODES. CONTRACTOR'S RESPONSIBILITY INCLUDES STRUCTURAL 10. IF RTUS ARE INSTALLED BEFORE ROOFING ENGINEER'S CERTIFICATION ON DETAILS JAPPROVED FJ LF_ 'COOPY w. ISSUE BLOCK Building Official Review and aUWLC`I_T0 H&,j j9wS;,jzfZ- uN A, At, Required Prior To Changes, Modiftations, Date or Alterations 235 MBIA Separate Application And Permits Required Sewer/Water Connection Heating and Air Conditioningj RTU -36 Fire Alarm System 10 TON Plumbing ROOF_... ETR DRAINS CETR U4 TYP) CHECKED BY, ic 4 828 MBH TO MAU ETR 2 BOAS -1 M 1 60 MBH,-,._ VERIFY GAS PRESSURE PRIOR TO START OF WORK 1/4"G ETR REFER TO MANUFACTURER'S INSTALLATION INSTRUCTIONS FOR ROUTING OF LIQUID AND SUCTION LINES TO ROOF MOUNTED CONDENSING UNITS. MAINTAIN ALL REQUIRED WORKING CLEARANCES, TYP OF ALL) DRAWINGS AND MAY NOT REFLECT EXACT "AS -BUILT" THOROUGH KNOWLEDGE OF ALL DliAWNU,5 ANU MECHANICAL ROOF PLAN CONDITIONS. CONTRACTOR SHALL FIELD VERIFY ALL SPECIFICATIONS IN THEIR RELATED FIELD. THE FAILURE EXISTING CONDITIONS PRIOR TO SUBMITTING FINAL TO ACQUAINT THEMSELF WITH THIS KNOWLEDGE DOES 114" V-041 BIDS. CONTRACTOR SHALL CAREFULLY COORDINATE NOT RELIEVE THE RESPONSIBILITY OF PERFORMING THE SHEET: NEW WORK AND DEMOLITION WITH ALL OTHER WORK PROPERLY. NO ADDITIONAL COMPENSATION DISCIPLINES AND EXISTING CONDITIONS, SHALL BE ALLOWED BECAUSE OF CONDITIONS THAT OCCUR DUE TO FAILURE TO FAMILIARIZE WORKERS WITH M 1 THIS KNOWLEDGE- CONDENSATE TO DRAIN AWAY FROM UNIT DOWN SIDE 17. FLEXIBLE DUCT CONNECTIONS TO NEW OR SLOPE OF ROOF, 7. CONTRACTOR SHALL INSTALL OWNER RELOCATED DIFFUSERS AND GRILLES ARE FURNISHED RTU CURB AND TEMPORARY PROHIBITED. INSPECT CONDITION OF SEE SPECIFICATION FOR ADDITIONAL INFORMATION, COVER CURB PER ARCH DETAIL (IF EXISTING DUCT AND REPLACE DAMAGED USED), RTU'S SHALL BE FURNISHED BY DUCT WITH EQUIVALENT TYPE OF DUCT AS OWNER AND INSTALLED BY CONTRACTOR. REQUIRED, CURB ADAPTOR (IF USED) SHALL BE FURNISHED BY OWNER AND INSTALLED BY 18. DUCT SIZES SHOWN ON DRAWINGS ARE NET CONTRACTOR RTU SHALL BE SET ON FREE AREA, CONTRACTOR'S OPTION, ROOF CURB. DO NOT SET RTU DIRECTLY ROUND DUCTWORK OF EQUIVALENT FREE 2WY O4HOURSPRIORTOSHUTTINGDONANN ROOF- COORDINATE RTU AREA MAY BE USED IN LIEU OFFHVACSYSTEMS, HVAC SYSTEMS, OR ENERGY INSTALLATION WITH WAL-MART RECTANGULAR. INCREASE RECTANGULAR MANAGEMENT CONTROLS SYSTEMS, SEND E- CONSTRUCTION MANAGER AND AES AS SHEET METAL SIZE AS REQUIRED FOR WALMART.COM. THE MAIL TO NSRM@ ' REQUIRED FOR RTUIAHU CURB ADAPTERS, LINER, REFER TO SPECIFICATIONS FOR SHALL STATE WHAT, WHY, AND WHEN IT IS THE INSULATION THICKNESS. BEING SHUT DOWN AND HOW LONG IT IS & REPLACE FILTERS ON NEW RTU NO MORE ANTICIPATED TO BE DOWN. THEN SEND A THAN ONE DAY PRIOR TO STARTING TEST 19. DUCT SUPPORT AND GRILLE DETAIL IS FOLLOW UP EAMAIL TO NSRlv!@WALMART,COM & BALANCE PROCEDURES. FILTERS SHALL APPLICABLE THROUGHOUT THE STORE, DO AFTER THE WORK IS COMPLETE AND THE BE 2" THICK EQUAL TO FARR 30/30. NOT USE FASTENERS THAT PENETRATE ROOF SYSTEM IS BACK UP AND RUNNING. DECK, 9. LABEL RTU WITH 6" BLACK PERMANENT PAINT STENCIL AND LABEL SENSOR WITH 20, TYPICAL BRANCH DUCT FITTING DETAIL IS 2" Hf(3H BLACK PERMANENT PAINT APPLICABLE THROUGHOUT THE STORE. STENCIL, NUMBER THE SENSOR TO CORRESPOND WITH RTU IT CONTROLS, 21. PROVIDE SEISMIC BRACING BASED ON LOCATE LABEL FOR UNIT NEAR ITS APPROPRIATE SEISMIC ZONE REQUIREMENTS DISCONNECT SO IT IS READABLE FROM PER SMACNA PUBLISHED SEISMIC DETAILS, ROOF HATCH. LOCAL AND NATIONAL CODES. CONTRACTOR'S RESPONSIBILITY INCLUDES STRUCTURAL 10. IF RTUS ARE INSTALLED BEFORE ROOFING ENGINEER'S CERTIFICATION ON DETAILS JAPPROVED FJ LF_ 'COOPY w. ISSUE BLOCK Building Official Review and aUWLC`I_T0 H&,j j9wS;,jzfZ- uN A, At, Required Prior To Changes, Modiftations, Date or Alterations 235 MBIA Separate Application And Permits Required Sewer/Water Connection Heating and Air Conditioningj RTU -36 Fire Alarm System 10 TON Plumbing ROOF_... ETR DRAINS CETR U4 TYP) CHECKED BY, ic 4 828 MBH TO MAU ETR 2 BOAS -1 M 1 60 MBH,-,._ VERIFY GAS PRESSURE PRIOR TO START OF WORK 1/4"G ETR REFER TO MANUFACTURER'S INSTALLATION INSTRUCTIONS FOR ROUTING OF LIQUID AND SUCTION LINES TO ROOF MOUNTED CONDENSING UNITS. MAINTAIN ALL REQUIRED WORKING CLEARANCES, TYP OF ALL) DRAWINGS AND MAY NOT REFLECT EXACT "AS -BUILT" THOROUGH KNOWLEDGE OF ALL DliAWNU,5 ANU MECHANICAL ROOF PLAN CONDITIONS. CONTRACTOR SHALL FIELD VERIFY ALL SPECIFICATIONS IN THEIR RELATED FIELD. THE FAILURE EXISTING CONDITIONS PRIOR TO SUBMITTING FINAL TO ACQUAINT THEMSELF WITH THIS KNOWLEDGE DOES 114" V-041 BIDS. CONTRACTOR SHALL CAREFULLY COORDINATE NOT RELIEVE THE RESPONSIBILITY OF PERFORMING THE SHEET: NEW WORK AND DEMOLITION WITH ALL OTHER WORK PROPERLY. NO ADDITIONAL COMPENSATION DISCIPLINES AND EXISTING CONDITIONS, SHALL BE ALLOWED BECAUSE OF CONDITIONS THAT OCCUR DUE TO FAILURE TO FAMILIARIZE WORKERS WITH M 1 THIS KNOWLEDGE- 1 12: I REFER TO SPLIT SYSTEMS MANUFACTURER m INSTALLATION INSTRUCTIONS FOR ROUTING 4 \ OF LIQUID AND SUCI'IOt LINESS TO ROOF _ s M3 1 MOUNTED CONDENSING UNITS, LINES SHALL MOUNT SPLIT SYSTEMS LOW BE KEPT AS STRAIGHT AS POSSBILE IN A ENOUGH BELOW STRUCTURE TO WORKMAN LIME MANNER. (TYP ALL) At -LOW FOR EASE OF SERVICING- J L i FOR SHARED CLASSROOMS WITH I LENNOX OS7500 PROGRAMMABLE THERMOSTAT (#13HI5) AND (2) ZONE SENSORS (47W37) THE SYSTEM SETUP FOR INDOOR SENSOR SETTINGS SHALL BE SET TO REMOTE 0k (OPTIONOPTIN #2 . 6 . I t yy'^' 4D I CD - r CD8IFORSINGLELARGECLASSROOM / r # WITH ST ANDALONE LENNOX CS7500 t y 10 175 CLASSROOM 1170 175 / 1 36a M3 r 2 £ PROGRAMMABLE THERMOSTAT (# 13H15 THEYSI-EM .`SETUP FOR Ij (TYP) INDOOR SENSOR SETTINGS SHALL B ' x :- SET TO INTERNAL (OPTION #3). -y r 12I - ' "' 3„ k' Y C( s t CLASSROOM _ RO,EEXJSTINCRTU36a 10 TON ON ROOF 10 I 361.1 6 CJt 9aIS F sAw E eID10L Er r ,5 , ~< 24110 5 f CC} ,, 1t1 . Ir10 vkLI a0 yy _ 3aa_j Y gg z 32=0 E 4 5 , , J3I4 A. rr, 39 F z301£' i 6 i s d y AHU2qRA , . 8 c { rF 5 x ¢ I E RAG CLASSROOM v - 150 t t 15, 1 a a 0^ _ 10 1`„ kFLAGRAG r i SAG ca n i15 , 15 II r_ 10 ,, ,< `, 150 1553 CDy. ewxe......wl.csk ,. , .,,.v ... :m ...... , .,.> , ,,: „ .,., „............> . a, 5 t, !a. I' ,: .. ,:, u,r., ,,.M.s,_.:. ,,,,,,,,,,;,,, ., ., roab ,..cvosen..:- .,:<: t GENERAL NOTES REFER TO SHEET M1 FOR GENERAL NOTES PERTAINING TO THIS SHEET MECHANICAL KEYNOTE 15.703 ROUTE DUCTWORK TIGHT TO THE BOTTOM OF STRUCTURE, COORDINATE WITH OTHER DISCIPLINES, 15.705 CONNECT TO EXISTING SUPPLY]RETURN DUCTWORK. INDICATED. 15.722 COORDINATE DUCT PENETRATIONS THROUGH ROOF, AND ROUTING OF DUCTWORK WITH CONDUITS, FIRE PROTECTION PIPING, LIGHTS AND STRUCTURE, rx.uss w P y ' gypA 6C ,. O n - . 6,++' FILEY { R r j6xw " iZ. liiJYWC 0 Lu, ' tda 0 GgLdLrc' r'T ' ga HELD EidS T.,_5> i i V E 5t Date apo LU tu.r c9 , G 71 any > JtoN c !? zwc azlz LW' r j6xw " iZ. Ny°tl IR 2.0aw 0 Lu, ' tda 0 zq=lozO " w9 wcy0 zt.j zo apo ti M65010010 1euaxmzf°a nazis Wn_i zcxn rw 2 ff LLJ ISSUE BLOCK C 1 09128116 ADD#1 a I - RAG RAG 360 T ; ... -- _....._n RAG AHU3 , i_. _ .._._ i n,. . CHECKED BY: !CtRAGii 10 , 10' CD RAG D L loll DISCHARGE AIR TEMP SENSOR. € 60 360 C3360 DRAWN BY: DCBSHIPPEDLOOSEWITHUNIT, 10 0 $ u> 6w., AHU2 v IINSTALLEDBYCONTRACTOR)- RE, 720 S cv 360 E ( 1 a0 MANUFACTURER'S INSTRUCTIONS FOR PROPER INSTALLATION. 12 192 AHU1 __-.._ „ _ ' PROTO; 195 S PROTO CYCLE; 07129/16i 1123DOCUMENTDATE. 08117 6 CD S-AHU4 ti M3 8" o 15:7x3 r . k - " HALLWAY AHU ASO E CEILING, I TS 8' } I M3 CM3 I DOAS-# ON ROOF (TYP) RAW NOTFt7R YFj24"124250CONSTRUCTION F,2: 10]J x,. 6 RAG I AHU4I ' S0_ 20"118" OFFICE 18" AREA .J 5-36 6ac3It 0 C___D 0 Lu, ' tda pyo/ A krmiws 0 LLJ L Q ca e C/J f 0 Lu CE) ' D z m ISSUE BLOCKC 1 09128116 ADD#1 a I - RAG RAG 360 T ; ... -- _....._n RAG AHU3 , i_. _ .._._ i n,. . CHECKED BY: !CtRAGii 10 , 10' CD RAG D L loll DISCHARGE AIR TEMP SENSOR. € 60 360 C3360 DRAWN BY: DCBSHIPPEDLOOSEWITHUNIT, 10 0 $ u> 6w., AHU2 v IINSTALLEDBYCONTRACTOR)- RE, 720 S cv 360 E ( 1 a0 MANUFACTURER'S INSTRUCTIONS FOR PROPER INSTALLATION. 12 192 AHU1 __-.._ „ _ ' PROTO; 195 S PROTO CYCLE; 07129/16i 1123DOCUMENTDATE. 08117 6 CD S-AHU4 ti M3 8" o 15:7x3 r . k - " HALLWAY AHU ASO E CEILING, I TS 8' } I M3 CM3 I DOAS-# ON ROOF (TYP) RAW NOTFt7R YFj24"124250CONSTRUCTION F,2: 10]J x,. 6 RAG I AHU4I ' S0_ 20"118" OFFICE 18" AREA .J 5-36 6ac3It 0 EQUIPMENT 3 LmIN. 1.112" O r SEE NOT E i HiGH DRAIN PARI WITH 130"ITOM I CO rare i;IzAiN_PIPE SEAL DRAIN PAN VOTH r NEOPRENE WASHERS AT SUPPORT RODS _— - _.I SEE NOTE 5 SOLDER FLANGE TO INSIDE OF DRAIN PAN L. ='+ W14,4" MIN NOTES; 1. SPIN -IN FITTINGS W/SCOOPS ARE NOT ACCEPTABLE 2, REF PLANS FOR RUNOUT SIZES. 145' LEAD IN, BRANCH DUCE' FITTING NTS 07,31.,15 MECH2.1-5 TOP CHORD OF ,FOIST 3' —TCP BEAM ROOF CLAMP TYP { MAX f O/ ! 1!1!1 X THREADED ROD TYP m...._ LOADS MUST BE J NYLON WIRE TIE (PAN DUiT — SCHEDULE 40 PVC PIPE HUNG WITHIN 3" f f #BT4LH,.l OR EQUIVALENT) AT EACH NYLON WIRE TIE, OF PANEL POINTS `- l (TYPICAL) f' APPROX 10" LONG (INNER DIAMETER OF PVC PIPE APPROX. SAME AS OD OF BOTTOM OF - . , f - INSULATION) STRUCTURE - 71 SUCTION LINE - tj , f j i + E l `i ,l` I _LIQUID LINE PIPING INSULATIONPIPIhGINSULATION \"; - s tom, f 1 1 5/1"x1 5/8" GALVANIZED TIGHT TO UNISTRUT P-1130(}; 6-0" UNISTRUT MAXIMUM ON CENTERS NOTE: FOR OVERHEAD LINES, UNISTRUT HORIZONTAL, TRAPEZE HUNG FOR PIPING BEHIND CASES, UNISTRUT VERTICAL., VVALL-MOUNTED HORIZONTAL HVA RI E ANT LINE SUPPORT DETAIL NTS 03130112 REFRIG-4 MECHANICAL SYMBOLS 11112 RECTANGULAR DUCT 13" WIDE a BY 12" DEEP 12 -" 12` DIAMETER ROUND DUCT 0-71 SUPPLY DUCT IN SECTION I RETURN OR EXHAUST DUCT IN 1 SECTION C3'avtY ELBOW WITH TURNING VANES TEE WITH TURNING VANES ROUND (OR OVAL) ELBOW VOLUME/BALANCE DAMPER H47 UC7Uifl.Oal.u[ia.t-- SUPPLY AIR DIFFUSER WITH ROUND SUPPLY DUCT 4- RETURN RETURN SJR EXHAUST AIR DIFFUSER x....._4,3 WITH ROUND DUCT CD DIFFUSER OR GRILLE TYPE 12" BRANCH DUCT AND/OR NECK SIZE 450 CFM T ` U H 1 THERMOSTAT S TIMER S#...._; TEMP SENSOR CONNECT TO EXISTING ETR EXISTING TO REMAIN FD ; FIRE DAMPER TS TEMPERATURE SENSOR r APPROVEDFILE COPY 19E,a psi c.A CODE LD iflqSq TOFF BEAM CLAMP TYP TOP CHORD OF JOIST 3., ! f --ROOF a._,.•.0n.-.:.,n az,,,,,,.,,,,..y...,.n.•......,,. MAX"._ e R}OF 2"x2"x114" ANGLE OR 51 1 511"x1 5111" UNISTRUT 5a, HANGER STRAP wI a 3 z ow" xa 0-71 a G1 -Z0— 0-fi'C76 SC C3'avtY Ul ,SL, -0w0 C"J,_. z U7 '2 Q G d.',G LL yC W C: 'i1 W H47 UC7Uifl.Oal.u[ia.t-- 0 3 z M C"J,_. z 0 0 F- j x....._4,3 c1r) I 0 LOADS MUST BE — ___ _..._ __.-_ .._._.. _ ...n.. HUNS WITHIN 3" i ' THREADED ROD ' hrtl'N. - SHEET METAL CHECKED BY: JC OF PANEL POINTS f q TYP SCREWS TYP OF EXISTING s' STRUCTURAL JOISTS I _"'_ L DRAWN BY DCB 60" MAX.. L PROTO: 195 Sc f RECTANGULAR DUCT , ~' ._ 2 "x2"x' 14" ANGLE OR P R 0 T 0 CYCLE: 07/29116 SUPPORT PER MANUFACTURERS 1 51Y,''x1 611" UNISTRUT _.. _ RECOMMENDATIONS. REF STRUCTURE. BOTTOM OF RECTANGULAR DUCT RECTANGULAR IJtiC 7 DOCUMENT DATE: 01/17/16 CONDENSING UNIT STRUCTURE PERPENDICULAR TO STR UC? SIL AIVI O PIP PING P-10 BLOT• PIES t T CH/ 7T (T' MBR/ SIDE VIEW SECTION NOTE: PLACE SUPPORT AT EVERY ELBOW AND SUPPORT EVERY 10'-0", DO NOT ATTACH BLOK TO ROOF PIPING SUPPORT(ONF NTS 03.28.14 REFRIG21-2 RTU (AHU SIM) RTU AHU SIM.) BRACKET -- BRACKET CHOOSE CHOOSE TOP OR 12 TEK SCREINS BQTTC)M # 10 TEK SCREWS I TOP OOR TYP EIGHT PER OM ROW (TYP EIGHT PER ROW BRACKET} BRACKET) — --— NEW CURES I NEW CURB 10 GA 18 GA GALV GALV TYP STRAP TYP ADAPTERR -- MU TERS AHU BRACKETMUNMJlAHUBRACKETLf1YOUT C)THER MANUFACTURERS SIMILAROTHERMANUFACTURERS,SIMIE.AR L-.,,. _._ REF SUPRI LER FOR _ L_ w _.e _ CURB ADAPTER TO RTU BRACKET ATTACHMENT j EXISTING CURB GAiCONNECTIONTYP G 1C} GA PROVIDE MIN _ CURB TYP` CONNECTION OF 10 BRACKET } I TEK SCREWS AT 6"OC. TYP i ROOT` ry 3& 10 TUN RTU WITH CURB ADAPTER 5 TON BRACKET ATTACHMENT 03/16 ` SCREW HOLES FOUR PER ROW EQ SPACED TYP' `— CHOOSE TOP OR BOTTOM ROW 18 GA GALV STRAP TYP LENNOX L NNOX RTU BRACKET LAY UT RTU BRACKET COTE: USE 6 ANCHOR BRACKETS FOR RTU'S (3, 5, 10 20 TON) ON ALL STORES EXCEPT WHERE LOCATED WITHIN 1500 FEET OF A SHORELINEORCOASTLINE (A SHORELINE IS ANY BODY OF WATER THAT WIND CAN FLOW FOR A DISTANCE OF AT LEAST 1 MILE), FOR THESE RTU INSTALLATIONS, USE 8 ANCHOR BRACKETS FOR 3, 5, AND 10 TON RTU'S AND USE 10 ANCHOR. BRACKETS FOR 20 TON RTU'S. FOR EACH AHL! PROVIDE A MINIMUM OF 8 (12 RECOMMENDED) ANCHOR BRACKETS. ANCHOR BRACKETS ARE FURNISHED BY AES INDUSTRIES, INC. BRACKET CONSTRUCTION, QUANTITIES, AND SPACING SHOWN ON THIS DETAIL ARE FOR GENERAL COORDINATION ONLY. INSTALL BRACKETS ACCORDING TO CURB MANUFACTURER/BRACKET SUPPLIER'S INSTALLATION INSTRUCTIONS AND PER ALL LOCAL CODES, COORDINATE FINAL BRACKET LOCATIONS WITH EQUIPMENT, DO NOT OBSTRUCT OPENING OR UTILITY CONNECTIONS. RTU/AHU N ACK TS NO'S 081.1$.10 MECH2.1-11 Luu u > u o 0 Lu u- p W u...L. U. 8 ,y 1 r8 8, 3t"f 11r.1 FROM UNIT uTOREGULATORVENT Ll u„ y 4 ice- , J - LOCATE REGULATOR VETT t c z u ;"8mo.FJM-q?_'`< ' TEE V111CAPPEi"31t8" I fiJIINIMUMOFI}'-{' rFROM --, o" <;W PRESSURE GAUGE OUTSIDE AIR INTAKES 0 cry z , 2 CONNECT ii t t CL oa 1 f7co ozap cfa.lt n,cr4frc5crna©nf.,xcr aPRESSUREREGULATOR; UNION — l / f INSTALL AT HEIGHT OF AHU/RTU GAS CO iNECTIO'N UNLESS REQUIRED OTHERWISE BY AHJ WITH RELIEF VENT FACING IN THE CLOWN Z)NI POSITION, SET DELIVERY PRESSURE TO 7 IN, j UNIT W,C. FOR NATURAL GAS (11 IN. W, C, MUNTE RS)t J! _ 11 IN, W.G. FOR PROPANE. REF GAS PRESSURE t i GAS REGULATOR SCHEDULE ` CONNECTION, wz Li f I t1iUh1ERE APPLICABLE) U.L LISTED BALL GAS VALVE REF SPECIFICATIONS; NO zo ROOF FIFE SUPPORT SUBITITUTIONS PERMITTED Wz I EQUAL: T ) MIFAB CSE5-10 (APPLICABLECURET ~ ; FOR UNSUPPORTED PIPE REF ROOFTOP PIPESPANNINGOVER36") z BLOCKING DETAIL ROOF T'FULL SIZE SEDIMENT TRAP x 60" MIN T ROOFTOP EQUIPMENT T NT MECH2-207.31.15 co COPY Q ci i rv. Luu u > u o 0 Lu u- p W u...L. U. 8 ,y 1 r8 8, 3t"f 11r.1 FROM UNIT uTOREGULATORVENT Ll u„ y 4 ice- , J - LOCATE REGULATOR VETT t c z u ;"8mo.FJM-q?_'`< ' TEE V111CAPPEi"31t8" I fiJIINIMUMOFI}'-{' rFROM --, o" <;W PRESSURE GAUGE OUTSIDE AIR INTAKES 0 cry z , 2 CONNECT ii t t CL oa 1 f7co ozap cfa.lt n,cr4frc5crna©nf.,xcr aPRESSUREREGULATOR; UNION — l / f INSTALL AT HEIGHT OF AHU/RTU GAS CO iNECTIO'N UNLESS REQUIRED OTHERWISE BY AHJ WITH RELIEF VENT FACING IN THE CLOWN Z)NI POSITION, SET DELIVERY PRESSURE TO 7 IN, j UNIT W,C. FOR NATURAL GAS (11 IN. W, C, MUNTE RS)t J! _ 11 IN, W.G. FOR PROPANE. REF GAS PRESSURE t i GAS REGULATOR SCHEDULE ` CONNECTION, wz Li f I t1iUh1ERE APPLICABLE) U.L LISTED BALL GAS VALVE REF SPECIFICATIONS; NO zo ROOF FIFE SUPPORT SUBITITUTIONS PERMITTED Wz I EQUAL: T ) MIFAB CSE5-10 (APPLICABLECURET ~ ; FOR UNSUPPORTED PIPE REF ROOFTOP PIPESPANNINGOVER36") z BLOCKING DETAIL ROOF T'FULL SIZE SEDIMENT TRAP 60" MIN T ROOFTOP EQUIPMENT T NT MECH2-207.31.15 co COPY CLASSROOM IT SCH_EL(OWNER FURNISHED) J- I- EVAPORATOR SECTION ELECTRIC a CONDENSING SECTIO N S MOK E CONDENSER DETECTOR MARK AREA SERVED MANUFACTURER MODEL REFRIGERANT CFM SEER/COP V/PH MCAIMOCP (K CONDENSING i MCAlMCCPLOCATION C NOTES T - X 4! P - 410A 1 720 14.7 20611 28130 `3 208/1 17,9/30 RA A-EH' 1t U f CLASSROOM #1 LENNOX CB 32MV 02 14H X 024.. { _.__.. ....___ r- 17 1301 RA A - DF2 ! 8 208.1 9P 410A 720 1 4 7 208(1 8 30AHU21CU2-}CLASSR(OOM #2 j LENNOX i CB32MV-0241 4H X 02 ' , AHU3/CU3 CLASSROOM #3 LENNOX CE3X32MV-024/'I4HPX-02 410A 720 14.7 20811: 28130 8 20611 17.9130 RA A-D,F AHU4/CU4 j OFFICE/HALLWAY LENNOX CBX32MV-018/14HPX-018 l 410A 560 14.7 29611 2F3J30 6 2(}811 12.1120 RA i A-E ALL ITEMS ON THIS SCHEDULE ARE OWNER FURNISHED AND GENERAL CONTRACTOR INSTALLED, NOTES: A. PROVIDE INSULATED REFRIGERATION PIPING PER MANUFACTURER'S RECOMMENDATIONS, 3, DIVISION 16 CONTRACTOR TO PROVIDE DISCONNECT SWITCH FOR EVAPORATOR SECTION AND CONDENSING SECTION. WITH LOW AMBIENT KIT, IFURNISHEDryRNI EAD WI OC ' UNIT U S LUGSi IT CONDUCTOR SIZES SHOWN OND. INDOOR AIR HANDLING UNIT IS FURNISHED WITH FACTORY SINGLE POINT POWER KIT Mak LB-&2009CA. COORDINATE SIZE t'F CONDUCTOR TERMINATftiJI J LUG. WITH CCS U.. ELECTRICAL DRAWINGS, POWER SHALL BE SINGLE -POINT CONNECTION. E UNIT IS FURNISHED WITH WALL MOUNTED THERMOSTAT #13H15 AND LOCKING GUARD COVER #39P21 BY UNIT MANUFACTURER; 7 'I1- ' F_ UNIT IS FURNISHED WITH VV,4LL MGLINTLCJ "i-I-II=RMC7STAT #13i -I15 (CS7500), LOCKING GUARD COVER #39P21, AND (2) INDOOR WALL SENSOR #47W37 !3Y UN MANUFACTURER, NATURAL GAS PRESSURE REGULATOR SCHEDULE E D'ICATED OUTDOOR AIR HANDLING OMIT SCHEDULE MARK AAON MODEL # AREA SERVED SUPPLY FAN CEM ESP MTR IN) (HP) EXHAUST IAN JFD CFM ESP MTR VFD TH Y/N) (IN) (1fP} (Y/N) 1, (MBH) I LESCOOLINGCOILPREHEATHEATINGCOILE SH EAT- I LAT TYPE INPUT TYPE INPUT EAT LAT MCA MJCP MBH) (DBiWB) {EBAAJB} _.0 _ KW MSH (DBIWB) (Dl3PJVB) SMOKE WEIGHT DETECTOR LBS V/PH LOCATION ROUND DOAS-1 RQ-01}5-3-V-EA09-313 , GCJC - DOA - COKD -GAA f1DEA0BE EG U000000TX I ACADEMY 1,1110 1.5 1.0 Y 1,{300 54.,.0) C3.5 Y 59 8 36.6 84170 t` C. 1 .. Ta41a21:: "T .RIC v....__I._._r,W_._...._.,e...w...... C),f3 GAS a___ 6CI.f 411131 81/52 23 2a 46013 P.A 1366 GENERAL INFORMATION (ALL UNITS): 112 SFT13 SBR-VCD 81 1920 1. UNITS FURNISHED BY t0`WNER, INSTALLATION AND START UP BY CONTRACTOR, 6 - 9 718 x 1 CONTACTS: CARNES I 2, PROVIDE 2"MERV 8 FILTERS IN SUPPLY AIRSTREAM AND 2" MERV 8 FILTERS IN EXHAUST AIRSTREAM. 3/4-1 8-14 112 x 9/16 A,C,D,E 3, PROVIDE WITH HEAT WHEEL. FOR SPACE NEUTRAL SUPPLY AIR, CEILING DIFFUSER 05.25.07 4, UNITS ARE PROVIDED WITH HACR-TYPE RATED CIRCUIT BREAKER. 440-674 B - 31R w" 11/4-11/4 8`12 5, UNITS ARE PROVIDED WITH SINGLE POINT POWER AND GAS ENTRY CONNECTIONS. 675-1674 I B - 34SR 2 - 2 6, ROOF CURB FURNISHED BY OWNER AND INSTALLED BY CONTRACTOR, REFER TO SPECIFICCATIONS, MAXITROL 0-4 25 2 L35 - 5 T MAKE FINAL COMPRESSOR WIRING TERMINATIONS ON ROTATION -SENSITIVE COMPRESSORS. N/A B'C'D 24 X 24 426 1250 8. UNITS ARE PROVIDED WITH FACTORY INSTALLED CONVENIENCE RECEPTACLE. 11 CARNES BCE SURFACE 9. INSTALL ANCHOR BRAC:HETS FURNISHED BY AES INDUSTRIES, INC. CONTACT; CHAD BURT AT 1 (800) 786-0402 314 7-11 m...__ mmN1A ._",•_ Nf _ 10. SMOKE DETECTORS ARE FACTORY INSTALLED. 325 ,u 5L60t1 1 7-11 g ED FILE Y 11, DISCHARGE AIR SENSOR IS SHIPPER LOOSE `,KITH EQUIPMENT FOR INSTALLATION BY (CONTRACTOR, 466 - 1250 325 - 7AL2Cl1D 1 '114 1 112 — rax=v1rverF0 FOR DUDE 12. RETURN AIR TEMPERATURE AND HUMIDITY SENSOR IS SHIPPED LOUSE WITH EQUIPMENT FOR INSTALLATION BY CONTRACTOR. GENERAL INFORMATION (ALL REGULATORS): 1. MINIMUM INLET PRESSURE 1.5 PSI; SET OUTLET PRESSURE TO 7 INCHES WATER COLUMN UNLESS NOTED OTHERWISE. 2. VERIFY CAPACITY SHOWN ON PLANS WITH CAPt,,CITY SCHEDULED FOR EACH REGULATOR MANUFACTURER BEFORE ORDERING. CAPACITIES VARY BETWEEN MANUFACTURERS. 3, REGULATORS MUST BE Z21.30/CSA 6.22 APPROVED, i Sub L`T TO FIELD INSPECTION NOTES: B. PROVIDE WITH VENT PROTECTOR FOR OUTDOOR USE. C. FOR MUNTERS UNIT USE SPRING °RANGE TO SET OUTLET PRESSURE AT 11 INCHES OF WATER COLUMN, j D. APPLICABLE FOR 2PSIG GAS SYSTEMS, UNITS ARE FURNISHED WITH FACTORY INSTALLED CONTROLS THAT COMMUNICATES VIA BAC NET PROTOCAL. E. APPLICABLE FOR 5PSIG GAS SYSTEMS. CONTACT INFORMATION: ITRON-MIDWEST GAS EQUIPMENT, INC: 1-877.962-8808; MAXITROL 1 1-248-356-1400. CLASSROOM IT SCH_EL(OWNER FURNISHED) J- I- EVAPORATOR SECTION ELECTRIC a CONDENSING SECTIO N S MOK E CONDENSER DETECTOR MARK AREA SERVED MANUFACTURER MODEL REFRIGERANT CFM SEER/COP V/PH MCAIMOCP (K CONDENSING i MCAlMCCPLOCATION C NOTES T - X 4! P - 410A 1 720 14.7 20611 28130 `3 208/1 17,9/30 RA A-EH' 1t U f CLASSROOM #1 LENNOX CB 32MV 02 14H X 024.. { _.__.. ....___ r- 17 1301 RA A - DF2 ! 8 208.1 9P 410A 720 1 4 7 208(1 8 30AHU21CU2-}CLASSR(OOM #2 j LENNOX i CB32MV-0241 4H X 02 ' , AHU3/CU3 CLASSROOM #3 LENNOX CE3X32MV-024/'I4HPX-02 410A 720 14.7 20811: 28130 8 20611 17.9130 RA A-D,F AHU4/CU4 j OFFICE/HALLWAY LENNOX CBX32MV-018/14HPX-018 l 410A 560 14.7 29611 2F3J30 6 2(}811 12.1120 RA i A-E ALL ITEMS ON THIS SCHEDULE ARE OWNER FURNISHED AND GENERAL CONTRACTOR INSTALLED, NOTES: A. PROVIDE INSULATED REFRIGERATION PIPING PER MANUFACTURER'S RECOMMENDATIONS, 3, DIVISION 16 CONTRACTOR TO PROVIDE DISCONNECT SWITCH FOR EVAPORATOR SECTION AND CONDENSING SECTION. WITH LOW AMBIENT KIT, IFURNISHEDryRNIEAD WI OC ' UNIT U S LUGSi IT CONDUCTOR SIZES SHOWN OND. INDOOR AIR HANDLING UNIT IS FURNISHED WITH FACTORY SINGLE POINT POWER KIT Mak LB-&2009CA. COORDINATE SIZE t'F CONDUCTOR TERMINATftiJI J LUG. WITH CCS U.. ELECTRICAL DRAWINGS, POWER SHALL BE SINGLE -POINT CONNECTION. E UNIT IS FURNISHED WITH WALL MOUNTED THERMOSTAT #13H15 AND LOCKING GUARD COVER #39P21 BY UNIT MANUFACTURER; 7 'I1- ' F_ UNIT IS FURNISHED WITH VV,4LL MGLINTLCJ "i-I-II=RMC7STAT #13i -I15 (CS7500), LOCKING GUARD COVER #39P21, AND (2) INDOOR WALL SENSOR #47W37 !3Y UN MANUFACTURER, NATURAL GAS PRESSURE REGULATOR SCHEDULE VOLUME/BALANCE CAMPER SCHEDULE TYPE W -_. MANI3FACTURERIMODEL hawwcir ROUND MANUFACTURER CAPACITY MODEL BODY SIZE SPRING MINIMUM I NOTES NOTES RANGE NUMBER INLET-OUTLET RANGE ORIFICE SBWM. VCD, RECTANGULAR CFH} 575B 4 R INCHES) 3(4 1 IN WC) S:5 9 IN) 12x9,16 I ADE.. ITRON 576 8801 B - 31 R 11/4 - 1 114 4 9 112 SFT13 SBR-VCD 81 1920 B_:.: 34SR:. 2-2 6 - 9 718 x 1 CONTACTS: CARNES I 0-439 B - 42R 3/4-1 8-14 112 x 9/16 A,C,D,E TLC SMD SISNEROS BROTHERS - (800) 499-0106 CEILING DIFFUSER 05.25.07 t•C3 3C ITRON 440-674 B - 31R w" 11/4-11/4 8`12 112 C D > E 675-1674 I B - 34SR 2 - 2 8.5-12.5 7/8 x 1 MAXITROL 0-4 25 2 L35 - 5 3/4-1 711 m -___ N/A B'C'D 24 X 24 426 1250 325 " 7AL z 1/4 - 1 112 11 CARNES BCE SURFACE 0 _ ..320 325.- 5L48 314 7-11 m...__ mmN1A ._",•_ Nf _ MAXITROL321 465 325 ,u 5L60t1 1 7-11 M NIA'__. TITUS E,H. PRICE CARNES 466 - 1250 325 - 7AL2Cl1D 1 '114 1 112 — 7 11 NIA GENERAL INFORMATION (ALL REGULATORS): 1. MINIMUM INLET PRESSURE 1.5 PSI; SET OUTLET PRESSURE TO 7 INCHES WATER COLUMN UNLESS NOTED OTHERWISE. 2. VERIFY CAPACITY SHOWN ON PLANS WITH CAPt,,CITY SCHEDULED FOR EACH REGULATOR MANUFACTURER BEFORE ORDERING. CAPACITIES VARY BETWEEN MANUFACTURERS. 3, REGULATORS MUST BE Z21.30/CSA 6.22 APPROVED, i NOTES: A, FURNISHED WITH INTERNAL RELIEF VALVE. B. PROVIDE WITH VENT PROTECTOR FOR OUTDOOR USE. C. FOR MUNTERS UNIT USE SPRING °RANGE TO SET OUTLET PRESSURE AT 11 INCHES OF WATER COLUMN, j D. APPLICABLE FOR 2PSIG GAS SYSTEMS, TITUS E. APPLICABLE FOR 5PSIG GAS SYSTEMS. CONTACT INFORMATION: ITRON-MIDWEST GAS EQUIPMENT, INC: 1-877.962-8808; MAXITROL 1 1-248-356-1400. 04.24.15 24 X 24 VOLUME/BALANCE CAMPER SCHEDULE TYPE W -_. MANI3FACTURERIMODEL hawwcir ROUND AES RUSKIN MANUFACTURER SISNEROS STYLE WMVCD WMRS25 NOTES BROTHERS Q MODEL SBWM. VCD, RECTANGULAR AES RUSKIN SUPPLY AIR SISNEROS CARNES AMD4 WMD25 24 X 24 BROTHERS T'MS SCD ( SFT13 SBR-VCD NOTE NO SUBSTITUTIONS ALLOWED, `REFER TO SPECIFICATION FOR ACCESSORIES fUPP.,.YA.R CONTACTS: CARNES I µCEILING ROUND NECK AES - (800) 786-0402 1 X 122 B D E U RUSKIN - (816) 761-7476 TLC SMD SISNEROS BROTHERS - (800) 499-0106 CEILING DIFFUSER MOUNT 05.25.07 t•C3 3C ROOFTOP E UIPMENT PIPiN-P RUNOUT EQUIPMENT CONDENSATE CAS PIPE SIZE DRAIN DOWNSTREAM- SIZE OF REGULATOR DOAS 3/4' 314 GENERAL INFORMATION: 1 RUNOUT SIZES ARE FOR INDIVIDUAL, PIECES OF EQUIPMENT. REFER TO ROOF PLAN FOR COMBINED LINES SIZES. 2. GAS PIPE SIZES REFLECT A MAXIMUM 10'-0" PIPE LENGTH FROM REGULATOR TO APPLIANCE. 3, CONDENSATE PIPE SIZE IS DOWNSTREAM OF 4" REDUCER. REFERENCE CONDENSATE DRAIN/SUPPORT DETAIL. 07.29.11 ui a DEVICE SCHELEAIRCRCI hawwcir TMARKSERVICE MANUFACTURER STYLE FRAME TYPE FACE SIZE NOTES o Q MODEL U Wu. tuJ:' CD SUPPLY AIR TITUS E,H. PRICE CARNES ROUND NECK LAY -IN 24 X 24 B, D, E T'MS SCD ( SFT13 DIFFUSER 1 fUPP.,.YA.R T E.H. ItTITUSEI- PRICE CARNES I µCEILING ROUND NECK SURFACE 1 X 122 B D E U CO2 y TLC SMD SKFA CEILING DIFFUSER MOUNT 24 X 24 t•C3 3C SUPPLY AIR TITUS E.H, PRICE f CARNES ROUND NECK LAY -IN 24 X 24 C D > E A _Ut,11tUM AA ASCD SFAB CEILING DIFFUSERER CD4 TMS- SUPPLYAIR ALUMINUM TITUS E.H. PRICE TDC-AA AMT? CARNES SEFA ROTUND NECK CEILING DIFFUSER SURFACE MOUNT 24 X 24 C, D, E. U c D5 SUPPLY AIR I TITUS E"H, PRICE CARNES ROUND DECK SURFACE REF C, D, E, I i SAI UMINUNI _ f TMRA-AA ARCD SSAA KXRA) CEILING DIFFUSER PJIC3UNT DRAWINGS CL0 SUPPLY AIR TITUS E,H. PRICE CARNES ROUND NECK LAY -IN 24X 2_4C D E, i4f^ - TD.A AA AMD FFCEILINGDIFFUSER CD7 SUPPLY A:R TITUS EH.PRI E mSKEA CARNES ROUND NECK LA( -IN 1 24 X 24 3 DE, Q TDCA SMDA SKTJ CEILING DIFFUSER_.____ rz-,',,)-P-AY-1NexI_Y AIR L 1HART' & COOLEY ROUND NECK I _ 24 4X2 RBD S FPD3CEILING DIFFUSER SAW' SIJPPLY AIR TITUS E,H. PRICE _ S CARNES DUCT MOUNTED? SURFACE REF B, E, F, I 30ORS 520DS R TDBV WALL REGISTER MOUNT DRAWINGS SAW! SI'JPPI Y AIR TITUS E.H. PRICE CARNES PLENUM SLOT SURFACE REF C, D, E, K SLOT DIFFUSER Fl_ - 20-j JS -220 CDFMC DIFFUSER MOUNT DRAWINGS SAW2 SUPPLY AIR TITUS E.H. PRICE CARNES LINEAR BAR REF C, D, E I~ -AR BAR CT -540 BPH25B CNB DIFFUSER DRAWINGS SLV SUPPLY AIR TITUS E.H. PRICE LINEAR VANE SURFACE REF C, D, E LINEAR VANE LL -1 LV1 DIFFUSER ._, MOUNT DRAWINGS D131 SUPPLY AIR AES DROP BOX A, G, H ADB -6-25 DIFFUSER._ , D132 SUPPLY AIR AES DROP BQX A, G, H ADB -6-10 DIFFUSER DB3 SUPPLY AIR AES DROP BOX A, G, H DB4 SUPPLY AIR i ADB 6`20 I AES DIFFUSER DROP BOX A, G, H A08-1-20 DIFFUSER B6 SUPPLY AIR AES DROP BOX A, G, H ADB -1-10 DIFFUSER DB5 i SUPPLY AIR i AES DROP BOX I A, G, H AD8-1 5 DIFFUSER DE7 I SUPPLY Alli AES DROP BOX A, G, H ADB -1-8 _ AES DIFFUSER DROP BOX A G HD38UIPL_Y /SIT? ADB -1.12 DIFFUSER I FPT FAN POWERED I TITUS E.H. PRICE TERIMINAL ,... ' ATQP02,08 FEV -20-08 CARNES VARIABLE VOLUME ASEG-08-B PARALLEL FLOW L, M, N, P M TC,1J TRANSFER R <tIR TITUS L.H. PRICEiCE RG\N RETURN AIR 33RL 1 91L CARNES FIXED BLADE SURFACE RSHAH WALL GRILLE MOUNT REF DRAWINGS B, E B, E TGW1 AIR_ TITUS E.H. PRICE CARNES FIXED BLADE SURFACE REF C, ETRANSFER RGW1 RE FURN AIR 63FL 99L R.AJMH WALL GRILLE MOUNT DRAWINGS 24 C, E TG TRANSFER AIR TITUS E,H. PRICE CARNES 1/2" EGGCRATE LAY-IN X 24 C, E RAG RET fRN AIR 5OF 80 RAPAH CEILING GRILLE C E, F EAG EXEwiAUST SIR (T r'Plw ,3 C, E, F TxG1 TRANSFER AIR $ TITUS E.H. PRICE CARNES 1/2" EGGCRATE SURFACE 12X 12 C. E RAG1 RETURN AIR 5OF 80 EACa1 EXHAUST AIR (TYPE 1) RAPAF CEILING GRILLE MOUNT CE,F C, E; F, I TG2 TRANSFER AIR_ TITUS E.H. PRICE CARNES 1/2" EGGCRATE SURFACE 24 X 24 C; D, E RAG2 I RETURN AIR 5OF 80 RAPAF CEILING GRILLE t MOUNT SCC, D, E, F EA.G2 EXHAUST ATR (TYPE 1) C D E F I TG3 RETURN AIR TITUS E.H. PRICE CARNES 112„ EGGCRATE LAY -IN 24 X 24 C, E, F, J RAGE (REMOVABLE 5OFF 8OFF RAPAF CEILINGGRILLEC, E, F, J EAG3 GRILLE) (TYPE 3) C, E, F, J RAG4 RETURN AIR HART & COOLEY 1/2" EGGCRATE LAY -IN 24 X 24 C, F, R, S REST _ ARD SUPPLY AIR TITUS E.H. PRICE CEILING GRILLE. CARNES ROUND NECK NONE VARIES S, D, T i XC -310 RID SSDB ROUND DIFFUSER GENERAL,. INFORMATION (ALL DEVICES): 1. THIS SCHEDULE IS COMPREHENSIVE. ALL MARKS MAY OR MAY NOT BE USED ON THE PLANS. DOTES: A. 6 -WAY (061-D133) OR 4 -WAY (DB4-DB8) THROW UNLESS SHOWN OTHERWISE WITH FLOW ARROWS ON PLAN, B. ALL. STEEL CONSTRUCTION. C, ALL ALUMINUM CONSTRUCTION, D. BRANCH DUCT SIZE SHALL BE SAME AS NOTED DIFFUSER NECK SIZE UNLESS NOTED OTHERWISE. E, STANDARD WHITE FINISH. F. PROVIDE NECK FOR DUCT CONNECTION, G. DROP BOX DIFFUSERS FURNISHED BY DOWNER INSTALLED BY CONTRACTOR. REFERENCE SPECIFICATIONS, H. PROVIDE INTEGRAL OPPOSED! BLADE DAMPERS ON ALL DRUM LOUVERS ON DROP BOXES WITH BRANCH DUCT +IVORK ATTACHED TO 'THE SUPPLY PLENUM.. I. PROVIDE MANUFACTURER'S OPPOSED BLADE DAMPER IN NECK. J. PROVIDE WITH FASTENERS FOR COMPLETE (NON -HINGED) REMOVABILITY OF GRILLE, DO NOT PROVIDE FILTER UNLESS TOTED OTHERWISE. K. TWO 2" SLOTS WITH MANUFAC T URER'S INSULATED PLENUM (TITUS FBP1, PRICE JSPI, CARNES CXPC). L. SET PRIMARY AIR MINIMUM TO 40 CFFA AND MAXIMUM TO 300 CFM. M. ELECTRICALCAL INFORMATION, 3 KW ELECTRIC HEAT, 277V SINGLE PHASE, AND FACTORYMOUNTED DISCONNECT. N. UNIT HEAT SHALL BE CONTROLLED BY, MANUFACTURER'S REMOTE MOUNTED 24V THERMOSTAT- REFERENCE PIANS FOR THERMOSTAT LOCATION. P, PROVIDE FACTORY -INSTALLED, PRESSURE INDEPENDENT, ELECTRONIC CONTROL PACKAGE WITH FACCTOR`E` INSTALLED CONTROL POWER. TRANSFORMER Q. REFER TO PLANS FOR DIRECTIONAL ARROWS INDICATING CFM THROWS FOR PROPER GRILLE SELECTION. R. FIXTURES SUPPLIED BY HJC (HAINES, JONES & CADBURY); CONTACT CUSTOMER SERVICE (800) 459-7099, S. STANDARD BLACK FINISH. T GRAY FINISH, U. PROVIDE Cc1LIN(5 TRANSITION REGISTER BOX INITH 16" OR 24" PLATE FOR ROUGH -IN. 01 27,12 ui a hawwcir U7 sLLiWLL CCW U acxrlal jvLLofye-' z za>- In" do='ILL d n j 'p" 'w' o Q KE°wo cum U Wu. tuJ:' L i}d 3. .u.X WW I c::D C-- 0 r LuW Il 0 `D 0I—I C lI i} 0 Co ISSUE BLOCK' CHECKED BY: ,1C DRAWN BY: DCB P'ROTO 195 SC PROTO CYCLE: 07/29/16 DOCUMENT DATE: 08117/16 NGT FOR CONSTRUCTION MECHANICAL SCHEDULES SHEET: KAA