2026-00042CITY OF MONTICELLO
505 WALNUT STREET
MONTICELLO, MN 55362-
63) 295-3060 FAX: (763) 295-4404
ADDRESS 9320 CEDAR ST S
PIN 155207001010
LEGAL DESC MONTICELLO BUSINESS CTR 3RD ADDN
LOT 001 BLOCK 001
PERMIT TYPE PLUMBING
PROPERTY TYPE COMMERCIAL
CONSTRUCTION TYPE ALTERATION
VALUATION 60,000.00
APPLICANT
UP FRONT PLUMBING
4080 LATOKA VIEW LANE SW
ALEXANDRIA, MN 56308-
320) 815-4159
OWNER
WAL-MART REAL EST BUSINESS TR
1301 LOTH ST SE
PROP TAX DEPT #8013
AR 72716-0555
AGREEMENT AND SWORN STATEMENT
I agree that the work will be conducted in conformance with
the ordinances of the City of Monticello and with the
Minnesota State Building Code. I understand that the work
will be in accordance with the plan that has been approved
by the Building Official. I agree that any damage caused to
public property including but not limited to curb, sidewalk,
public utilities a6d,si n 11 be repaired at my expense.
Applicant
Date l- 5- Z O Z
Bldg Official Date
Z 0 Z 6- 0 0 0 4 z
DATE ISSUED: 01/23/2026
Permit #: 2026-00042
PLUMBING BASE FEE, COMM
STATE SURCHARGE, PLBG VAL
TOTAL
Payment(s)
CREDIT CARD 8958
900.00
30.00
930.00
930.00
SEPARATE PERMITS REQUIRED FOR WORK OTHER THAN DESCRIBED ABOVE.
CITY OF
Moniiceflo
BUILDING SAFETY
COMMERCIAL / IND
Permit No.
Date )
PERMIT APPLICATION
505 Walnut Street, Suite 11 Mnnti :QnQ444X5__ -
buildingdepartment@MonticelloMN.gov
SITE ADDRESS
3320 cedar street
LEGAL DESCRIPTION
LOT
PLAT
BLOCK
OWNER (Name)
wal-mart stores
OWNER'S E-MAIL ADDRESS:
NA
P1D. NUMBER
ZONED
763-295-3060
Address)
2001 SE 10th street
Tel. No.)
CONTRACTOR (Name) (Address)
UpFront Plumbing Jayme Aure 4080 Latoka View Lane SW
CONTRACTOR'S LICENSE NUMBER (IF APPLICABLE)
PM063443
CONTRACTOR'S E-MAIL ADDRESS:
upfrontplumbing 18@gmail.com
ARCHITECT (Name)
ARCHITECT'S E-MAIL ADDRESS
ENGINEER Name)
ENGINEER`S E-MAIL ADDRESS:
320) 815-4159
Address)
Address)
Tel. No.)
Tel. No.)
Tel. No.)
DESCRIPTION OF
WORK:
Remodel of front an drear bathrooms. replacing mopsinks/faucets in some areas.swn
pu11sinsansooonawa
s in Iludl. prep areas. the
walls are o en. same with Grab and o trenches will have u roughinforthefloordrainsthatareusedfortheconnder
round and desate
drains for the coolers.
TYPE OF WORK (Please Circle One) TYPE OF CONSTRUCTION (Please Circle One)
New Commercial
Addition Industrial
Alteration Institutional
Repair Multi -Family
Move Other commerical
Other commerical
ADDITIONAL INFORMATION MISC. NOTES:
Valuation: $60,000
Construction Type: remodel plumbing
Occupancy Group: NA
Square Footage: NA
of Stories: 1
Maximum Occupancy: Na
Fire Suppression: Yes No
ESTIMATED VALUE OF CONSTRUCTION
I hereby apply for a permit for construction as described and acknowledge that the information I haveprovidedaboveiscompleteandaccurate. I agree that the work will be conducted in conformance with
the ordinances of the City of Monticello and with the Laws of the State of Minnesota; and that I under- stand that this application is not a permit and that the work is not to start without a permit. I further un-
derstand that the work will be in accordance with the plan that has been approved by the Building Offi- cial. I agree that any damage caused to public property including but not limited to curb, sidewalk, pub- lic utilities and signs will be repaired at my expense.
Applicant Signature --
Print Name / Title Jay e Aure Owner
Date 12/30/2025
Approved by Building Official:
Approved by Fire Marshal
Date Approved: 4 C%f Total Permit Fee:$
LDate:
iaeljQ
DEPARTMENT OF ROVED FILE Copy
LABOR AND INDUSTRY EpFORCODECOMPLIANCE
FIELD INSPE N
Division of Construction Codes and Licensing
REPORT ON PLUMBING PLANS
PROJECT: Walmart 3624 Remodel, 9320 Cedar St., Monticello, Wright County, Minnesota,
Plan No. PB-R2504-0062
OWNERSHIP: Walmart Stores Inc., Cathy Yockey, 2001 SE 1 Oth Street, Bentonville, AR 72716
SUBMITTER: Cathy Yockey, WD Partners, 7007 Discovery Blvd, Dublin, MN 43017
Plans Dated: See Stamped Plans
Initial Date Received: April 9, 2025
Last Date Received: April 11, 2025
Date Approved: June 13, 2025
This review is limited to the provisions of the Minnesota Plumbing Code, Minnesota Rules, Chapter 4714 and
assumes the data on which the design is based are correct. Approval is contingent upon meeting the requirements
listed below. A copy of the approved plans and this report must be retained at the project location.
INSPECTIONS: This project will be inspected by the local municipality. The contractor/installer must obtain
all required inspection permits from the Monticello Building Official, Robert Ferguson. All plumbing
installations must be tested and inspected in accordance with the requirements of the Minnesota Plumbing Code.
No plumbing work may be covered prior to inspection.
REQUIREMENT(S):
All plumbing shall be installed in accordance with Chapter 4714. All pipe, fittings, traps, fixtures,
materials, and devices shall be listed or labeled by a third -party listing agency and comply with the
applicable standards referenced in the code (see Sections 301.2 and 1701.1).
2. The re -use of existing fixtures is prohibited unless the fixtures conform to the current Minnesota Plumbing
Code (see part 4714.0101, subparts 3 and 4).
3. A single Double Check Valve Assembly is installed on the RO water supply to the misting system (PO 12)
and to the produce case cleanout system, as shown on Diagram 8/P I. Each point of use shall be separately
protected where potential cross -contamination of individual units exists (see Section 602.2). In order to
keep the design with one backflow preventer as you have shown, you must verify each system discharges
through a code approved air gap constructed in accordance with Table 603.3.1. In addition, you must verify
the existing reverse osmosis system does not serve any unprotected non -potable water systems.
4. If the floor drains shown on riser 3/P 1.1 are used as receptors, then they must be individually vented. All
floor drains except emergency floor drains, tell -tale floor drains, and floor drains not used as receptors must
be individually vented. The trap to vent distance for individually vented floor drains must meet Table
1002.2. All other floor drains must be installed within 25 feet of a vented branch or main (see Sections
418.2, 901.2, and 1002.2).
5. The vents for the new lavatories in the customer restrooms are not shown on the plumbing riser diagrams.
Fixture vents must rise within 45 degrees from the vertical at least 6 inches above the fixture flood level
before offsetting horizontally or connecting to a branch vent (see Section 905.3).
443 Lafayette Road N., St. Paul, MN 55155 • (651) 284-5005 • www.dli.mn.gov
An Equal Opportunity Employer
Walmart 3624 Remodel
Plumbing
Plan No. PB-R2504-0062
Page 2 of 3
06/13/2025
6. Trap primers must have an ASSE 1013 reduced pressure principle backflow preventer; an ASSE 1020
pressure vacuum breaker; or an ASSE 1056 spill -proof vacuum breaker (see Table 603.2). Trap primers
with integral backflow prevention are permitted only when equipped with one of the above -listed backflow
preventers.
7. Insert devices for floor drain trap seal protection are not permitted (see Sections 315.2 and 418.2).
8. Changes in direction in drainage piping must be made by appropriate use of wyes and bends (see Section
706.0). Sanitary tees are not allowed for vertical to horizontal or horizontal to horizontal direction changes.
9. The lavatories must have ASSE 1070/ASME A112.1070/CSA B 125.70 mixing valves or an ASSE 1084
water heater limiting the hot water temperature to 110 degrees Fahrenheit or less. Faucets must limit flow
to 0.5 gpm at 60 psi. Metering faucets may not exceed 0.25 gallons per cycle (see Sections 407.2 and
407.3). Accessible lavatories must meet Section 403.0.
10. Valves should be installed permitting the water supply to each individual fixture to be shut off without
disrupting any other portion of the building. An accessible control valve shall be installed ahead of each slip
joint connection at a plumbing fixture (see Section 606.5).
11. Each horizontal drain branch on or below the floor level of the building drain shall be provided with a
cleanout at its upper terminal with the following exceptions (see Section 707.4):
a. A cleanout is not required if the branch is less than five feet unless it serves sinks or urinals.
b. A cleanout is not required on a drain that is 72 degrees or less from the vertical unless it serves kitchen
sinks or urinals.
12. A cleanout should be provided where new waste and vent piping connects with existing for testing.
13. PVC solvent weld joints must use ASTM F656 purple primer and ASTM D2564 cement per Section
705.6.2.
14. The water distribution system shall be disinfected per Section 609.9.
15. The plumbing system shall be tested in accordance with Sections 609.4 and 712.0.
NOTE(S):
1. The scope of this project consists of remodeling an existing building. The plumbing installation includes
floor drains, a flush valve water closet, four 3-station lavatories, two 2-station lavatories, two lavatories, and
the potable water connection to a produce misting system.
2. The building is served by existing municipal sewer and water services.
3. The current Minnesota Plumbing Code, Chapter 4714, and related information can be found at:
http://www.dli.nm. gov/business/plumbing-contractors/2020-minnesota-plumbing
Authorization may be withdrawn if installation does not begin within one year. Additional requirements may
result from changed conditions or additional information.
Walmart 3624 Remodel
Plumbing
Plan No. PB-R2504-0062
Page 3 of 3
06/13/2025
Approved:
Caleb Buck
Public Health Engineer
Plumbing Plan Review and Inspections Unit
651 /284-5253
caleb.buck@state.mn.us
Corey Frain, P.E.
Public Health Engineer
Plumbing Plan Review and Inspections
651/284-5882
corey.frain@state.mn.us
www.dli.mn.gov/business/get-licenses-and-permits/plumbingplan-review
cc: Cathy Yockey, WD Partners
Robert Ferguson, Building Official
File
DEPARTMENT OF
LABOR AND INDUSTRY
December 23, 2025
Cathy Yockey
WD Partners
7007 Discovery Blvd
Dublin, MN 43017
Gentlemen/Ladies:
Subject: Plumbing at Walmart 3624 Remodel, 9320 Cedar St., Monticello, Wright County, Minnesota,
Plan No. PB-R2504-0062
On December 16, 2025, our office received revised plans dated November 20, 2025 for the above referenced
facility. The revised plans indicate a new ice maker, a relocated coffee maker, and replacing a breakroom sink, an
electric water cooler, mop sinks, lavatories, and water closets. The plans have been reviewed and were found to
conform to the Minnesota Plumbing Code with the following comments:
Ice machines must be protected with approved air gap or backflow prevention device(s) based on the
design of the equipment and the requirements of Minnesota Rules, Chapter 4714, Section 602.3 and Table
603.2.
2. Coffee makers must be supplied through an air gap or an ASSE 1022 backflow preventer with access and
clearance per the manufacturer's installation instructions (see Section 603.5.12).
This letter should be attached to our previous Report on Plans dated June 13, 2025. Please let me know if you
have any questions.
Sincerely,
4 61 -
Caleb Buck
Public Health Engineer
Plumbing Plan Review and Inspections Unit
651/284-5253
Caleb.Buck@state.mn.us
www.dli.mn.gov/business/get-licenses-and-permits/plumbing-plan-review
cc: Robert Ferguson, Building Official
WD Partners
Cathy Yockey, Walmart Stores Inc.
File
443 Lafayette Road N., St. Paul, MN 55155 • (651) 284-5005 • www.dli.mn.gov
An Equal Opportunity Employer
J t KVlvi HJJC 1 f+hlilN(; -- ""- %,ntUN NLATES FOR PLUMBING CDSPECIFICATIONS. PENETRATIONS THROUGH GROCERY CEILINGS AND Z wWALLS. PROVIDE AIR TIGHT SEAL AROUND PIPINGPENETRATIONSTHROUGHCOOLER/FREEZERAND O
rn
WALLSCEILINGS. FINISH WITH ESCUTCHEON PLATE. Z
33. PROVIDE HEAT TAPE AND INSULATION ON ALL WATERANDDRAINPIPINGEXPOSED
m
O
TO FREEZING.
34. INSTALL CONTINUOUS SEALANT JOINT AT ALLEXTERIORWALLPENETRATIONS. ISSUE BLOCK
PR#35. INSTALL VTR'S A MINIMUM OF 24" FROM ROOF EDGE
1
DD
08/1325
AND/OR PARAPET WALLS ADDSANDAMINIMUMOF10FTFROMOUTSIDEAIRINTAKEOFROOFTOPUNITS.
05 9/302 3CCD#1 11/20/25 36.
NOT USED. 37.
BUILDING COMPONENTS ABANDONED BY TH OFWORKSHALLE SCOPE BESECUREDECUREDTOPREVENTFALLING, LOOSENINGORDCREATINGTHEFUTURE. ING DAMAGE OF ANY KIND IN 6UUIIlUANG
SAF APPROVED
FILE COPY REVIEWED
FOR CODE COMPLIANCE SUBJECT
TO FIELD INSREC`tION Date:
Signature:
CHECKED
BY: RRN DRAWN
BY: AM
PROTO
CYCLE: 12/13/24 DOCUMENT
DATE: 03/25/25 u
III IIIIII, LICENSED
PROFESSIONAL '
s ENGINEER =
cn :%
53184 •'Q ;
j'•
1
NNE _ 1
hereby certify that this plan, specification, or report was Prepared
by me or under my directsupervisionandthatlamadulyLicensedProfessionalEngineerunderthelawsoftheStateofMinnesota. Jeffrey
P. Bolyard, PE 1 Date.
11 /20/2025 l License
No.: 53,84 DEPARTMENT
OF LABOR
AND INDUSTRY EE[
F HA
VE COMPLIANCE
WIT ANDS PLUMBING
H cowl CODE,
CHAP Orals, CHAPTER . --1 TS
THAT DO NOT ARCHITECT
OR OF
RECORD SEAL TURE
SHALL BE D
NOT FOR AL